26
Aermec cod. INRLLSIY 13_01. 4086991_00
NRL 800 - 1800
GB
pCO5)
CIRCULATING PUMP
1. Turn the unit on (ON)
2. Start Pump
3.
Flow switch or pressure switch (if provided)
4. Whenever alarms do not occur, the compressor
starts.
Reference parameters:
Compressor
ON
Temperature
3°C <
> 3°C
n° 2 -
See User Manual
Restart Manual
OFF
ON
Temperature > 5°C 4°C <
OFF
ON
Temperature > 5°C 4°C <
Only for pure water (not added with glycol)
WATER FLOW ALARM
the compressors and the pump
Water
Pump
ON
Flow Switch
or
Pressure Switch (if provided)
>20 seconds -
Compressor not work
Cod. Alarm See User Manual -
-
>20 seconds
Start Compressor
Versions with Total Recovery and Condensing
Units are equipped with GR3 electronics
(standard remote panel)
All the other versions have pCO5 electronics
(remote panel available as accessory)
12. ELECTRONIC CONTROL(PCO
5
)