EasyManuals Logo

AERMEC Variable Multi Flow ANL Series User Manual

AERMEC Variable Multi Flow ANL Series
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
18
18.03. 5719210_03
ANL / 290-650
EN
 
AllelectricalworksmustbecarriedoutbyPERSONNELWITHTHEAPPROPRIATELEGALQUALI-
FICATIONS,trainedandawareoftherisksrelangtosuchworks.
ThedesignofthecablingandrelatedcomponentsmustbecarriedoutbyPERSONNELWITH
APPROPRIATE QUALIFICATIONS TO DESIGN ELECTRICAL INSTALLATIONS, following interna-
onalandnaonalstandardsofthelocaontheunitisinstalled,inaccordancewithcurrent
legalrequirements.
Forinstallaondetailsrefertothe electricalwiringschemacssuppliedwiththe unit. The
electrical wiring schemac together with the manuals must be conserved with care and
MADEAVAILABLEFORFUTUREREFERENCE.
Theweatherproofsealsoftheequipmentmustbecheckedbeforemakingelectricalconnec-
onsandtheunitmostonlybepoweredoncompleonofallelectricalandhydraulicworks..
WARNING:


WARNING:
Verifythatallterminalsaretightonpower
carryingconductorsbeforefirststart-up
and30daysafterputtingintoservice.
Afterwardschecktwiceyearly.
Looseterminalscanresultinoverheating
ofcablesandcomponents..





 
L.R.A.
L.R.A.





 


IL
  








2




2

2

290 400V/3N/50Hz 2 4 130 99 47.1 3+N 1 10 5 1 10 63
300 400V/3N/50Hz 2 4 131 101 50.3 3+N 1 10 5 1 10 63
340 400V/3N/50Hz 2 4 162 123 56.0 3+N 1 16 5 1 16 80
400 400V/3N/50Hz 2 6 183 140 65.9 3+N 1 16 5 1 16 100
580 400V/3N/50Hz 2 2 262 198 84.8 3+N 1 25 5 1 16 125
620 400V/3N/50Hz 2 2 308 230 99.1 3+N 1 35 5 1 16 125
650 400V/3N/50Hz 2 2 320 242 111.7 3+N 1 35 5 1 16 160
L1 L2 


400V/3N/50Hz
TheANLunitsarefullyfactorywiredandonlyrequire
connecontothepowersupplynetwork,downstream
ofanisolator,inaccordancewiththeapplicablewiring
standardsofthecountryofinstallaon.
Itisrecommendedtocheckthefollowingitems:
1. Theelectricalnetworkiscapableofmeetingthe
electricalinputdatashowninthetablebelow.
2. Theunitisonlypowereduponcompletionof
anyhydraulicandelectricalworks.
3. Complywiththeindicatedphasingandearth
requirements.
4. Thepowersupplycablemusthavetheappropri-
ateprotectionagainstshortcircuits,residual
currentandearthleakagewithsuitableisolation
fromotherdevices.
5. Thetoleranceonthepowersupplyvoltageis
±10%ofthenominalvoltageratingoftheunit
(forthreephaseunitsamaximumimbalanceof
3%betweenphasesispermitted).Ifthesevalues
arenotmetpleasecontactthepowersupply
company.
6. Fortheelectricalconnectionsusedoubleinsu-
latedcablesinaccordancewithapplicablewiring
standards.

1. Amagneto-thermalcircuitbreakerconforming
toIEC-ENstandards(contactapertureminimum
3mm)isrequired,withadequateprotectionin
accordancewiththedataprovidedinthefollow-
ingtable,tobeinstalledascloseaspossibleto
theunit.
2. Aneffectiveearthconnectionisrequired.The
manufacturercannotbeheldresponsiblefor
anydamagescausedbylackof,orinadequate,
earthingoftheunit.
3. Forthreephaseunitscheckthecorrectcable
phasing.
Thecablecrosssectionsshowninthefollowingcable
aretherecommendedvaluesbasedonamaximum50
mcablelength.
Forlongercablelengthsordifferenttypesofcable
installations,theDESIGNERisresponsibleforcorrectly
sizingtheisolator,circuitbreaker,earthingprotection
andcablesizes,basedon:
Length
Typeofcable
Electricalinputoftheunit,distanceandoperat-
ingambients.
 

1. Beforemakingtheelectricalconnecons
ensurethattheisolatorisopen.
2. Openthefrontcontrolpanel.
3. Usetheholesprovidedinthelowerpartofthe
cabinetfortheelectricalpowersupplyandfor
otherexternalwiringconnecons.
4. Entercablesintothecontrolpanelonlythrough
theaperturesprovided.
5. Avoiddirectcontactwithun-insulatedcopper
tubesandcompressors.
6. Idenfytheterminalsforelectricalconnecon
withreferencetothewiringdiagramprovided
loosewiththeunit.
7. Takethepowercableintothecontrolpaneland
connecttoterminalsU-NandPEwithrespect

 Maximumcurrentinput
 Startingcurrent
 Powersupplyconnection
3+N: 3phase+neutral
 Control+safetiesconnection
 Earthconnectiontotheunit
 Mainisolator



Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC Variable Multi Flow ANL Series and is the answer not in the manual?

AERMEC Variable Multi Flow ANL Series Specifications

General IconGeneral
BrandAERMEC
ModelVariable Multi Flow ANL Series
CategoryChiller
LanguageEnglish

Related product manuals