21
18.03. 5719210_03
ANL / 290-650
EN
Toavoidexcessivecompressorstartstwofunconsare
provided.
- MinimumtimecompressorisOFF180seconds.
- MinimumtimecompressorisON120seconds.
Thewiringschemacprovidesoutputstocontrolthe
circulangpumps.Thesystempumpstartsimmediate-
lyandaer40secondsofoperaon,whenthewater
owisstabilised,thepressuredierenal/owswitch
controlfunconisenabled.Ifnoalarmsarepresent
theunitwillstart.
Thealarm
11
isalwaysacveeveninstandbymode.
Topreventdamagetotheplateheatexchangerby
freezingofthewaterwithintheunitisstoppedand
analarmraisedifthewatertemperaturedropsbelow
theminimuman-freezesetpointof3°C.Theunitcan
onlyre-startaeramanualresetandifthean-freeze
sensorreadsawatertemperatureabove4°C
12
.With
theunitinomodeandwithawatertemperature
below4°Cthefactoryedelectricheatersonthe
heatexchangerareturnedon,andturnedowhen
thewatertemperatureexceeds5°C.Thewaterpump
alwaysremainsacve.
Theunithasalowwaterowratealarmusingafac-
toryeddierenalpressureswitchorowswitch.
Thissafetyacvatesaertherst40secondsofpump
operaonifthewaterowrateisnotsucient.The
operaonofthisalarmstopsthecompressorsandthe
pump.
11
Theanti-freezesetpoint
canonlybeadjustedbyan
authorisedservicecentreand
onlyafterverifyingthatthe
hydrauliccircuithasthecor
-
rect%ofanti-freezesolution.
12
Ifthisalarmoccursimmediate-
lycalltheauthorisedtechnical
serviceassistance.
Itisforbiddentocarryoutanycleaningoperation
beforeisolatingfromthepowersupply
1
.
Confirmnovoltageispresentbeforecommencing
works.
Periodicmaintenanceisafundamentalrequirementto
ensureefficientunitoperationbothintermsofopera-
tionandenergyefficiency.
1. Watercircuitisfilled.
2. Waterfilterisclean.
3. Operationofthedifferentialpressureorflow
switch.
4. Absenceofairinthesystem(vent).
5. Waterflowrateisalwaysconstantthroughthe
evaporator.
6. Conditionofthehydraulicpipinginsulation.
7. Thepercentageofanti-freezeliquid,asmaybe
required
1. Operationofsafeties.
2. Powersupplyvoltage.
3. Electricalpowerinput.
4. Tightnessofconnectionsandterminals.
5. Operationofthecompressorcrankcaseheater.
1. Stateofcompressors.
2. Efficiencyoftheplateheatexchanger.
3. Operatingpressures.
4. Leakstoconfirmthecorrectoperatingrefriger-
antcharge.
5. Operationofthehighandlowpressurepres-
sostats
6. Efficientoperationofthefilterdrier.
ofcompressorsandelectri-
calpanelandexternalpanellingoftheunit.Poor
fixingscausenoiseandabnormalvibrations.
2. Thestateoftheunitstructure.
Treatanypartsshowingsignsofcorrosionwith
theappropriatepaintstoreduceoreliminate
rust.
TheANLunitsarefactorychargedwithR410Aand
tested.Innormaloperationtheythereforedonot
requireanyinterventionfromthetechnicalassistance
serviceinrelationtotherefrigerantcharge.Overtime
somesmallleakscanappear,causingdischargingthe
circuitandcausingamalfunctionoftheunit.Inthis
casetheleakshavetobefoundandrepairedandthe
unitrechargedinaccordanceandasrequiredunder
currentlegislationandgoodworkingpractices.
Ensurethatthedisposaloftheunitiscarriedoutin
accordancewiththecurrentlegalrequirements.
WARNING
Werecommendaservicelogbookis
providedfortheunit(responsibility
oftheuser)tokeeprecordsofany
worksontheunit,whichwillaid
maintenanceandrepairworks.Note
intheservicelogbookdate,typeof
works(routinemaintenance,inspec-
tionorrepair),describingtheevent
andthemeasurestaken.
Itistochargewith
refrigerantcircuitwitharefrigerant
typedifferenttothatindicated.Us-
ingadifferentrefrigerantcancause
seriousdamagetotheunit.