EasyManua.ls Logo

AERMEC Variable Multi Flow ANL Series - Location of Installation; Positioning

AERMEC Variable Multi Flow ANL Series
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
18.03. 5719210_03
ANL / 290-650
EN
 
Before proceeding with the installaon of the equip-
mentagreethelocaonwiththeclient,takingintoac-
countthefollowingpoints:
1. Thebasemustbeabletosupporttheweightofthe
unit.
2. The safe distances between the unit and other
equipmentorstructuresmustbestrictlyrespected
toensuretheintakeandoutletairisfreetocircu-
late.
3. Theequipmentmustbeinstalledbyacompetent
and qualied technician, in compliance with the
applicable naonal legislaon of the country of
desnaon, respecng the required minimum
maintenanceaccessspaces.
 
Beforeliingtheunitverifytheliingcapability
oftheequipmentbeingused,takingintoaccount
theinformaonprovidedwiththepackaging.
Whenliinginsertthroughtheunit'sbaseholes
liing bars (NOT PROVIDED) of sucient length
tolocatetheliingchainsandsafetylugs.
Posion the unit in the place indicated by the
client, inserng between the unit's base and
the base support a rubber pad (minimum 10
mmthick)oran-vibraonmounts.Forfurther
informaonrefertothedimensionaltables.
Securetheunitandensureitislevel;checkthat
sucient access is provided for hydraulic and
electricalconnecons.
In the case of installaon where gusts of wind
mayoccuradequatelysecuretheunit using ap-
propriatees.
WARNING:
Iftheunitisinstalledinparticularlywindy
locationstheprovisionofwindbarriers
maybenecessarytoavoidmalfunctions.
WARNING:
LiftingbarsareNOTprovided.

Related product manuals