Fan failure
Check if the fan is not turning or blocked by foreign object.
Heat sink over temperature
protection
When the temperature of the device is lower than the recovery temperature, normal
charge and discharge control is resumed.
Bypass overload protection, inverter
overload protection
Reduce the use of power equipment; Restart the unit to resume load output.
Inverter short circuit protection
Check the load connection carefully and clear the short-circuit fault points;
Re-power up to resume load output.
PV over-voltage
Use a multi-meter to check if the PV input voltage exceeds the maximum allowable
input voltage rated.
Battery missed alarm
Check if the battery is not connected or if the battery circuit breaker is not closed.
8.4
Battery Storage and Maintenance
8.4.1 Battery Storage Requirements
Do not put the battery into fire. The battery may explode.
Do not open or damage the battery. The electrolyte flowing out from the battery is harmful to the skin
and eyes. The electrolyte may also be toxic;
1.
When being stored, the batteries shall be placed correctly in accordance with the marks on the packing case. Do not
put them upside down or on the side.
2.
When stacking up the battery packing cases, the stacking requirements on the outer package shall be met.
3.
The batteries should be handled with care, and damage to batteries should be strictly prohibited.
4.
Requirements for the storage environment:
Ambient temperature: -10 to 55 , recommended storage temperature: 20 to 30.
Relative humidity: 5%RH-80%RH.
Dry, well ventilated, and clean.
The corrosive organic solvents, gases and other substances shall be kept away.
Exposing to direct sunlight shall be avoided.
The distance from the heat source should not be less than two meters.
5.
When being stored, the battery shall be disconnected from the external connection. If there is an indicator light on
the battery panel, the indicator light shall be off.
7.
The warehouse keeper shall make monthly statistics on the battery storage, and regularly inform the planning link of
the battery inventory. If any battery has been stored for nearly 15 months (-10 to 25 ), 9 months (25 to
35 ), or 6 months (35 to 55 ), recharging shall be arranged in time.
8.
When the stored batteries are going to be delivered, the first-in first-out principle should be followed.