2.3.2 Grounding Requirements
When installing the device to be grounded, the protective grounding wire must be installed first; when removing the
device, the protective grounding wire must be removed at last.
It is forbidden to destroy the grounding conductor.
It is forbidden to operate the device without a grounding conductor installed.
The device shall be permanently connected to the protective grounding wire. Before operating the device, electrical
connection of the device shall be checked to ensure that the device is reliably grounded.
2.4 Installation Environment Requirements
This product is for indoor use only, and is strictly prohibited to be used in outdoor environment.
Do not install or use this product in an environment where the temperature is lower than -10 or higher than 50 .
It should be installed in a dry and well-ventilated environment to ensure good heat dissipation performance.
The product can be installed at a maximum altitude of 2,000m.
The installation position should be away from the fire source.
The product should be installed and used away from children and animals.
The installation position should be far away from water sources, such as faucets, sewer pipes, and sprinklers, to
avoid entering of water.
The device should be placed on a firm and flat supporting surface.
Do not place any inflammable or explosive items around the device.
When the device is running, do not block the ventilation vent or heat dissipation system to prevent fire caused by
high temperature.
The operation and service life of the energy storage is related to the operating temperature.
The energy storage should be installed at a temperature equal to or better than the ambient
temperature.
CAUTION