18
-
95 Pa pour le mode hygroréglable (Hygro) lorsque l’EasyVEC
®
C4 ULTRA ou ULTIMATE est combiné à un système
standard sur bouches hygroréglables (sans chauffe-eau thermodynamique raccordé sur l’air extrait),
- 135 Pa pour le mode hygroréglable + T.Flow
®
lorsque l’EasyVEC
®
C4 ULTRA ou ULTIMATE est combiné à un système
T.Flow
®
Hygro+ et T.Flow
®
Nano sur bouches hygroréglables,
- 75 Pa pour le mode Autoréglable (Auto) lorsque l’EasyVEC
®
C4 ULTRA ou ULTIMATE est combiné à un système
standard sur bouches Autoréglables.
CONTROLS
Controlled P.
CONTROLLED P
Humidity-based
… T.Flow
®
CONTROLLED P
Humidity-based
… T.Flow
®
In the event of a controlled pressure operating mode, two pressure values are required by the box fan to operate:
- Minimum pressure (Pmin): it is defined automatically according to the type of ductwork: Hygro, T.Flow or Auto. Select
the type of corresponding ductwork and confirm.
- 95 Pa for the humidity-controlled mode (Hygro) when EasyVEC C4 ULTRA or ULTIMATE is combined with a standard
system on humidity-controlled terminals (without thermodynamic water heater connected to the exhaust air),
- 135 Pa for the humidity-controlled mode + T.Flow
®
when EasyVEC C4 ULTRA or ULTIMATE is combined with a T.Flow
®
Hygro+ and T.Flow
®
Nano on humidity-controlled terminals,
- 75 Pa for the self-balancing mode (Auto) when EasyVEC C4 ULTRA or ULTIMATE is combined with a standard system
on self-balancing terminals
CONSIGNE
P = 135 Pa
CONSIGNE
P = 130 Pa
CONSIGNE
P = 130 Pa
- La pression maximale (Pmax, 300 Pa max) : elle doit être saisie manuellement. Il est fortement recommandé de
renseigner la valeur indiquée dans le rapport d’étude Conceptor Ventilation. Diminuer ou augmenter la consigne avec
ou et appuyer sur pour valider.
SETPOINT
P = 135 Pa
SETPOINT
P = 130 Pa
SETPOINT
P = 130 Pa
- M
aximum pressure (Pmax, 300 Pa max): it has to be entered manually. It is highly recommended to insert the value
indicated in the Ventilation Conceptor study report. Reduce or increase the setpoint with or
and press
to confirm.
b.3. Saisir la pression de consigne (Pression constante) / Entering the setpoint pressure (Constant Pressure)
Se référer au paragraphe a.2 • Please refer to section a.2
b.4. Mode Expert / Expert Mode
Sélection chiffre en clignotement et non souligné • Selection figure blinking and not underlined
Pour accéder au menu Expert il est nécessaire de renseigner le code PIN : 4144 • To access the Expert menu, the
following PIN code has to be entered: 4144
RÉGULATION
Expert
EasyVEC Ultimate
Soft version 0.23
ID # 110349991
CHOIX LANGUES
Français
Anglais
CHOIX LANGUES
Français
PARAMÉTRAGE PARAMÉTRAGE
Régulation
RÉGULATION
P. Constante
… Expert
RÉGULATION
P. Constante
… Expert
RÉGULATION
Expert
… P. Constante
PARAMÉTRAGES
Régulation
… Reset
RÉGULATION
P. Constante
P. CONSTANTE
Hygro
… T.Flow
®
P. CONSTANTE
Hygro
… T.Flow
®
P. CONSTANTE
T.Flow
®
… P. Constante
PARAMÉTRAGE PARAMÉTRAGE
Régulation
… Reset
RÉGULATION
Expert
EXPERT
Q Constant
... 0-10 V
Pression
référence = 120 Pa
Pression
référence = 120 Pa
RÉGULATION
Press. Régulée
P. RÉGULÉE
Hygro
… T.Flow
®
P. RÉGULÉE
T.Flow
®
… P. Constante
Pression maximum
référence = 120 Pa
RÉGULATION
Expert
CODE PIN
4 1 4 4
EXPERT
Press. Régulée
... Vitesse Constante
EXPERT
Vitesse Constante
... Q Constant
Pression maximum
référence = 120 Pa
RÉGLAGES RÉGLAGES
Couleur
… Langues
RÉGLAGES
Langues
… N°série
LOG ERREUR-S LOG ERREUR-S
E25 : C4 détection
LOG ERREUR-S
E55 : Vit. moteur
pendant 3 s.
P. RÉGULÉE HYGRO
Pression = 120 Pa
Débit = 1450 m
3
/h
Vitesse = 2100 RPM
E49 : ID Produit
Confirmer
ID Produit
3474
P. RÉGULÉE
Press. min.
… Press. max.
RÉGLAGES
N° série
… ID produit
RÉGLAGES
Liaison Bluetooth
BLUETOOTH
Activer Bluetooth ?
RÉGLAGES
ID produit
… Nb ouïes
RÉGLAGES
Nb ouïes
Option gaz
RÉGLAGES
Nb ouïes
NOMBRE OUÏES
1
2
BLUETOOTH
Activé
RÉGLAGES
OPTION GAZ
Oui
Non
RÉGLAGES
Option gaz
OPTION GAZ
Oui
Non
ID Produit
3 4 7 4
P = 120 Pa
CONSIGNE
P = 135 Pa
CONSIGNE
P = 130 Pa
CONSIGNE
P = 130 Pa
P. RÉGULÉE
Hygro
… T.Flow
®
PARAMÉTRAGE
Régulation
RÉGULATION
P. Constante
… Press. Régulée
PARAMÉTRAGE
Press. Régulée
… Expert
RESET
Reset
LOG ERREUR-S
E31 : C4 détection
pendant 3 s.
EXPERT
0-10 V
EXPERT
Consigne min.
Consigne max.
EXPERT
Consigne max.
Consigne min.
CONSIGNE min. 0-10V
U1 = 2 V
V1 = 20 %
U1 = 2 V
Vitesse = 20 %
U2 = 10 V
Vitesse = 100 %
CONSIGNE max. 0-10V
U2 = 10 V
V2 = 100 %
RESET
Paramétrage
usine ?
P. RÉGULÉE HYGRO
P = 120 Pa
Q = 1250 m
3
/h
V = 1620 RPM
PARAMÉTRAGE
Reset
… Régulation
RESET
Reset
COM MODBUS
EasyVEC Ultimate
Soft version 0.23
ID # 110349991
LANGUAGES
French
English
LANGUAGES
English
CONFIGURATION CONFIGURATION
Controls
CONTROLS
Constant P.
… Controlled P.
CONTROLS
Controlled P.
… Expert mode
CONTROLS
Expert mode
… Constant P.
CONFIGURATION
Controls
… Reset
CONTROLS
Constant P.
CONSTANT P
Humidity-based
… T.Flow
®
CONTROLLED P
Humidity-based
… T.Flow
®
CONSTANT P
T.Flow
®
… Self-regulated
CONFIGURATION CONFIGURATION
Controls
… Reset
CONTROLS
Expert mode
EXPERT MODE
Const. airflow
… 0-10V
EXPERT MODE
0-10 V
EXPERT MODE
Min. reference
Max. reference
EXPERT
Max. setpoint
Min. setpoint
Min. setpoint 0-10V
U1 = 2 V
V1 = 20 %
U1 = 2 V
Speed = 20 %
U2 = 10 V
Speed = 100 %
Max. setpoint 0-10V
U2 = 10 V
V2 = 100 %
Pressure
reference = 120 Pa
Pressure
reference = 120 Pa
CONTROLS
Controlled P.
CONTROLLED P
Humidity-based
… T.Flow
®
CONTROLLED P
T.Flow
®
… Self-regulated
Maximum pressure
reference = 120 Pa
CONTROLS
Expert mode
PIN CODE
4 1 4 4
EXPERT MODE
Controlled P.
… Constant speed
EXPERT MODE
Constant press
Constant airflow
Maximum pressure
reference = 120 Pa
SETTINGS SETTINGS
Colour
… Language
SETTINGS
Language
… Serial number
ERROR-S LOG ERROR-S LOG
E25: C4 detection
ERROR LOG
E55: motor RPM
during 3 s.
Humidity-based
controlled pressure
Pressure = 120 Pa
Airflow = 1250 m
3
/h
Humidity-based
controlled pressure
Pressure = 120 Pa
Airflow = 1250 m
3
/h
Speed = 1620 RPM
E49 : Product ID COM MODBUS
Confirm
Product ID
3474
CONTROLLED P
Minimum press.
… Maximum press.
SETTINGS
Serial number
… Product ID
SETTINGS
Bluetooth link
BLUETOOTH
Activate Bluetooth ?
SETTINGS
Product ID
… Ventilation inlet nbr.
SETTINGS
Ventilation inlet nbr.
Gas option
SETTINGS
Ventilation inlet nbr.
VENTILATION INLET
1
2
BLUETOOTH
Activated
SETTINGS
Product ID
3 4 7 4
Pressure = 120 Pa
SETPOINT
P = 135 Pa
SETPOINT
P = 130 Pa
SETPOINT
P = 130 Pa
RESET
Factory
settings?
CONFIGURATION
Reset
… Controls
RESET
Reset
GAS OPTION
Yes
No
SETTINGS
Gas option
GAS OPTION
Yes
No
EXPERT MODE
Constant speed
Constant airflow
PIN CODE
4 1 4 4
S
ur les modèles ULTRA et ULTIMATE, le mode expert permet : • On the ULTRA and ULTIMATE models, the expert mode allows:
De renseigner dans le mode Pression régulée les pressions Min et Max (300 Pa Max) manuellement pour ajuster
le fonctionnement du caisson à l’installation: • The Min. and Max. pressures (300 Pa Max) to be entered in the
controlled pressure mode to adjust the operation of the box fan at installation:
EXPERT
Press. Régulée
EasyVEC Ultimate
Soft version 0.23
ID # 110349991
CHOIX LANGUES
Français
Anglais
CHOIX LANGUES
Français
PARAMÉTRAGE PARAMÉTRAGE
Régulation
RÉGULATION
P. Constante
… Expert
RÉGULATION
P. Constante
… Expert
RÉGULATION
Expert
… P. Constante
PARAMÉTRAGES
Régulation
… Reset
RÉGULATION
P. Constante
P. CONSTANTE
Hygro
… T.Flow
®
P. CONSTANTE
Hygro
… T.Flow
®
P. CONSTANTE
T.Flow
®
… P. Constante
PARAMÉTRAGE PARAMÉTRAGE
Régulation
… Reset
RÉGULATION
Expert
EXPERT
Q Constant
... 0-10 V
Pression
référence = 120 Pa
Pression
référence = 120 Pa
RÉGULATION
Press. Régulée
P. RÉGULÉE
Hygro
… T.Flow
®
P. RÉGULÉE
T.Flow
®
… P. Constante
Pression maximum
référence = 120 Pa
RÉGULATION
Expert
CODE PIN
4 1 4 4
EXPERT
Press. Régulée
... Vitesse Constante
EXPERT
Vitesse Constante
... Q Constant
Pression maximum
référence = 120 Pa
RÉGLAGES RÉGLAGES
Couleur
… Langues
RÉGLAGES
Langues
… N°série
LOG ERREUR-S LOG ERREUR-S
E25 : C4 détection
LOG ERREUR-S
E55 : Vit. moteur
pendant 3 s.
P. RÉGULÉE HYGRO
Pression = 120 Pa
Débit = 1450 m
3
/h
Vitesse = 2100 RPM
E49 : ID Produit
Confirmer
ID Produit
3474
P. RÉGULÉE
Press. min.
… Press. max.
RÉGLAGES
N° série
… ID produit
RÉGLAGES
Liaison Bluetooth
BLUETOOTH
Activer Bluetooth ?
RÉGLAGES
ID produit
… Nb ouïes
RÉGLAGES
Nb ouïes
Option gaz
RÉGLAGES
Nb ouïes
NOMBRE OUÏES
1
2
BLUETOOTH
Activé
RÉGLAGES
OPTION GAZ
Oui
Non
RÉGLAGES
Option gaz
OPTION GAZ
Oui
Non
ID Produit
3 4 7 4
P = 120 Pa
CONSIGNE
P = 135 Pa
CONSIGNE
P = 130 Pa
CONSIGNE
P = 130 Pa
P. RÉGULÉE
Hygro
… T.Flow
®
PARAMÉTRAGE
Régulation
RÉGULATION
P. Constante
… Press. Régulée
PARAMÉTRAGE
Press. Régulée
… Expert
RESET
Reset
LOG ERREUR-S
E31 : C4 détection
pendant 3 s.
EXPERT
0-10 V
EXPERT
Consigne min.
Consigne max.
EXPERT
Consigne max.
Consigne min.
CONSIGNE min. 0-10V
U1 = 2 V
V1 = 20 %
U1 = 2 V
Vitesse = 20 %
U2 = 10 V
Vitesse = 100 %
CONSIGNE max. 0-10V
U2 = 10 V
V2 = 100 %
RESET
Paramétrage
usine ?
P. RÉGULÉE HYGRO
P = 120 Pa
Q = 1250 m
3
/h
V = 1620 RPM
PARAMÉTRAGE
Reset
… Régulation
RESET
Reset
COM MODBUS
EasyVEC Ultimate
Soft version 0.23
ID # 110349991
LANGUAGES
French
English
LANGUAGES
English
CONFIGURATION CONFIGURATION
Controls
CONTROLS
Constant P.
… Controlled P.
CONTROLS
Controlled P.
… Expert mode
CONTROLS
Expert mode
… Constant P.
CONFIGURATION
Controls
… Reset
CONTROLS
Constant P.
CONSTANT P
Humidity-based
… T.Flow
®
CONTROLLED P
Humidity-based
… T.Flow
®
CONSTANT P
T.Flow
®
… Self-regulated
CONFIGURATION CONFIGURATION
Controls
… Reset
CONTROLS
Expert mode
EXPERT MODE
Const. airflow
… 0-10V
EXPERT MODE
0-10 V
EXPERT MODE
Min. reference
Max. reference
EXPERT
Max. setpoint
Min. setpoint
Min. setpoint 0-10V
U1 = 2 V
V1 = 20 %
U1 = 2 V
Speed = 20 %
U2 = 10 V
Speed = 100 %
Max. setpoint 0-10V
U2 = 10 V
V2 = 100 %
Pressure
reference = 120 Pa
Pressure
reference = 120 Pa
CONTROLS
Controlled P.
CONTROLLED P
Humidity-based
… T.Flow
®
CONTROLLED P
T.Flow
®
… Self-regulated
Maximum pressure
reference = 120 Pa
CONTROLS
Expert mode
PIN CODE
4 1 4 4
EXPERT MODE
Controlled P.
… Constant speed
EXPERT MODE
Constant press
Constant airflow
Maximum pressure
reference = 120 Pa
SETTINGS SETTINGS
Colour
… Language
SETTINGS
Language
… Serial number
ERROR-S LOG ERROR-S LOG
E25: C4 detection
ERROR LOG
E55: motor RPM
during 3 s.
Humidity-based
controlled pressure
Pressure = 120 Pa
Airflow = 1250 m
3
/h
Humidity-based
controlled pressure
Pressure = 120 Pa
Airflow = 1250 m
3
/h
Speed = 1620 RPM
E49 : Product ID COM MODBUS
Confirm
Product ID
3474
CONTROLLED P
Minimum press.
… Maximum press.
SETTINGS
Serial number
… Product ID
SETTINGS
Bluetooth link
BLUETOOTH
Activate Bluetooth ?
SETTINGS
Product ID
… Ventilation inlet nbr.
SETTINGS
Ventilation inlet nbr.
Gas option
SETTINGS
Ventilation inlet nbr.
VENTILATION INLET
1
2
BLUETOOTH
Activated
SETTINGS
Product ID
3 4 7 4
Pressure = 120 Pa
SETPOINT
P = 135 Pa
SETPOINT
P = 130 Pa
SETPOINT
P = 130 Pa
RESET
Factory
settings?
CONFIGURATION
Reset
… Controls
RESET
Reset
GAS OPTION
Yes
No
SETTINGS
Gas option
GAS OPTION
Yes
No
EXPERT MODE
Constant speed
Constant airflow
CONTROLLED P
Minimum press.
… Maximum press.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the aldes EasyVEC C4 and is the answer not in the manual?