Residential HRV/ERV
26
Mode Speed Description
--
Unit stops completely. Remains idle
regardless of the humidity level.
Yes Yes Yes Yes
Continuously exchanges air with the
outside at low speed.
Yes Yes Yes Yes
Continuously exchanges air with the
outside at high speed.
Yes Yes Yes Yes
Recirculates interior air at low speed. Yes No Yes Yes
Recirculates interior air at high speed. Yes No Yes Yes
ECO-1
Exchanges air for the rst 20 minutes,
followed by recirculation for 40 minutes.
Repeats every 60 minutes.
Yes No Yes Yes
ECO-2
Exchanges air for the rst 20 minutes,
then remains idle for the next 40
minutes. Repeats every 60 minutes.
Yes Yes Yes Yes
Executes a high-speed exchange
sequence for the selected period of
one, two, or four hours.
Yes Yes Yes Yes
When paired with the Aldes 611228
timer unit, high-speed air is exchanged
during its countdown interval.
Yes Yes Yes Yes
Automatically controls the level of
relative humidity by activating the high-
speed air exchange when the humidity
level exceeds the selected setpoint.
Yes Yes Yes Yes
Installing the Dehumidistat (P/N 611224)
Note: If the Dehumidistat is used to sense bathroom humidity, it should be mounted high on
a wall near the shower or tub for a faster response. It should also be set to a higher relative
humidity (70-80%) to avoid unnecessary high-speed exhaust.
1. Run a 2-conductor low-voltage (24V) electrical wire through
the wall until it reaches the HRV/ERV.
2. Select one of the three options on the next page for
wiring, according to the HRV/ERV model and your
specific ventilation requirements. Connect one end o f
each conductor to the Dehumidistat’s wires, and the other
end to the HRV/ERVs control terminal block according t o
the diagram.
Humidity Control
(P/N 611224)