Operation
Operation
Start-up
Duringstart-upcheckthatnovisibleleakagesappearfromplatepack,valvesorpipingsystem.
Caution!
BeforepressurizingthePHEitisimportanttoensurethatthetemperatureofthePHEis
withinthetemperaturerangestatedinthePHEdrawing.
Caution!
IfthetemperatureofthePHEisbelowtheminimumtemperatureforthegasketspriorto
theserviceitisrecommendedtoheatupthePHEabovethislimittoavoidcoldleakage.
Note!
Ifseveralpumpsareincludedinthesystem,makesureyouknowwhichoneshouldbe
activatedrst.
Centrifugalpumpsmustbestartedagainstclosedvalvesandvalvesmustbeoperatedas
smoothlyaspossible.
Donotrunpumpstemporarilyemptyonthesuctionside.
Note!
Adjustmentsofowratesshouldbemadeslowlyinordertoavoidtheriskofpressure
surge(waterhammer).
Waterhammerisashortlastingpressurepeakthatcanappearduringstart-upor
shut-downofasystem,causingliquidstotravelalongapipeasawaveatthespeedof
sound.Thiscancauseconsiderabledamagetotheequipment.
Step1
Beforestart-upcheckthatalltighteningboltsarermlytightened
andthatthedimensionAiscorrect,refertoPHEdrawing
Step2
Checkthatthevalveisclosedbetweenthepumpandtheunit
controllingthesystemowratetoavoidpressuresurge.
Step3
Ifthereisaventvalveinstalledattheexit,makesureitisfully
open.
DocumentIDLanguageEdition
3490010217EN2014-11InstructionManual-PlateHeatExchangers15