PowerMonitor 500 EtherNet/IP Device Profile Appendix C
Assembly Object Instances
The communication module Assembly Object supports nine instances (instances
100d to 108d). The Data attributes of these instances can be accessed via Class 1
scheduled connections and via Class 3 or UCMM unscheduled connections.
See Appendix A
, PowerMonitor 500 EtherNet/IP Device Profile for more
information on the content of the Assembly Instances.
Assembly Object Services
Assembly Instance Size (No. of elements) Data Type Data Table Description
100 20 UINT Product Information
101 12 REAL Real-time Voltage and Current
102 18 REAL Real-time Power, PF, Frequency
103 12 REAL Max Voltage and Current
104 17 REAL Max Power, PF, Frequency
105 12 REAL Demand Voltage and Current
106 17 REAL Demand Power, PF, Frequency
107 18 REAL Energy Meters
108 2 UINT Alarm and Output Status
Service Code Class/Instance Usage Service Name
0x0E Class/Instance Get Attribute Single