EasyManua.ls Logo

Allen-Bradley 1769-SDN - Installation Safety and Planning

Allen-Bradley 1769-SDN
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Publication 1769-UM009B-EN-P - May 2002
Installation and Wiring 3-3
General Considerations
Compact I/O is suitable for use in an industrial environment when
installed in accordance with these instructions. Specifically, this
equipment is intended for use in clean, dry environments (Pollution
degree 2
(1)
) and to circuits not exceeding Over Voltage Category II
(2)
(IEC 60664-1).
(3)
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B,
C, D or non-hazardous locations only. The following WARNING
statement applies to use in hazardous locations.
(1)
Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that
occasionally a temporary conductivity caused by condensation shall be expected.
(2)
Over Voltage Category II is the load level section of the electrical distribution system. At this level transient
voltages are controlled and do not exceed the impulse voltage capability of the products insulation.
(3)
Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC)
designations.
WARNING
!
EXPLOSION HAZARD
Substitution of components may impair suitability for
Class I, Division 2.
Do not replace components or disconnect
equipment unless power has been switched off or
the area is known to be non-hazardous.
Do not connect or disconnect components unless
power has been switched off or the area is known to
be non-hazardous.
This product must be installed in an enclosure.
All wiring must comply with N.E.C. article 501-4(b).