Publication 1769-UM009B-EN-P - May 2002
Configuring the DeviceNet Network 4-7
Setting the 1769-SDN Node Address
Once the network browse is complete, the node addresses appear to
the right of their icons. If you need to change a module’s node
address, use the following procedure.
Perform the following steps:
1. From the Tools menu select Node Commissioning. You will
see the Node Commissioning window.
TIP
You can use this procedure to change the node
address of other devices on the network (e.g., a
Photoeye). You can also change the network data
rate (baud rate) of some devices. Depending upon
the device, power may need to be cycled for baud
rate changes to take effect.
TIP
The controller must be in the Program mode, or the
scanner in the Idle mode (bit 0 of the Module
Command Array = 0), for the scanner to accept the
configuration information.
Allen-Bradley Drives