112 Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 4 Bulletin 290E/291E/294E Programmable Parameters
Starter Protection Group
OLResetLevel
This parameter determines the % Thermal
Capacity which an overload can be cleared.
Parameter Number 29
Access Rule GET/SET
Data Type BYTE
Group Basic Configuration
Units % TCU
Minimum Value 75
Maximum Value 100
Default Value 75
OverloadClass
This parameter provides the overload trip
classification.
1 = 10
2 = 15
3 = 20
Parameter Number 30
Access Rule GET
Data Type USINT
Group Basic Configuration
Units
Minimum Value 1
Maximum Value 3
Default Value 1
ProtFltResetMode
This parameter configures the Protection
Fault reset mode.
0 = Manual
1 = Automatic
Parameter Number 41
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0
TripStatus
This parameter provides the fault
condition that caused any current trip.
Parameter Number 42
Access Rule GET
Data Type WORD
Group Trip Status
Units
Minimum Value 0
Maximum Value 0xE3BF
Default Value 0