Rockwell Automation Publication 290E-UM001B-EN-P - June 2012 49
Installation and Wiring Chapter 2
6. The E-stop Out tee (Cat. No.: 898N-653ES-NKF) is used with cordset or patchcord to connect to the ArmorStart Distributed Motor Controller.
7. Control Power Receptacles – Female receptacles are a panel mount connector with flying leads (Cat. No.: 888N-D65AF1-*)
8. Three-Phase Power Trunk – Patchcord cable with integral female or male connector on each end (Example Cat. No.:280-PWRM35A-M*)
9. Three-Phase Drop Cable – PatchCord cable with integral female or male connector on each end (Example Cat. No.:280-PWRM22A-M*)
10. Three-Phase Power Tees and Reducer – Tee connects to a single drop line to trunk with quick change connectors (Cat. No.: 280-T35)
Reducing Tee connects to a single drop line (Mini) to trunk (Quick change) connector (Cat. No.: 280-RT35)
Reducer connects from quick change male connector to mini female connector (Cat. No.: 280-RA35)
11. Three-Phase Power Receptacles – Female receptacles are a panel mount connector with flying leads (Cat. No.: 280-M35F-M1)
Figure 24 - On-Machine Stop Stations
ArmorConnect Cable Ratings
The ArmorConnect Power Media cables are rated per UL Type TC 600V 90°C
Dry 75°C Wet, Exposed Run (ER) or MTW 600V 90°C or STOOW 105°C
600V - Canadian Standards Association (CSA) STOOW 600V FT2.
For additional information regarding ArmorConnect Power Media refer
to ArmorStart LT selection guide, publication 290-SG001_-EN-P.
Branch Circuit Protection Requirements for ArmorConnect
Three-Phase Power Media
When using ArmorConnect Three-Phase Power Media, fuses or circuit breakers
may be used for the motor branch circuit ground fault protection if properly
sized and allowed by product labeling.
Circuit Breaker:
Where ArmorStart LT is used with ArmorConnect — suitable for use on a
circuit capable of delivering not more than 10000 RMS Symmetrical Amperes
IMPORTANT
See the On-Machine Connectivity catalog for specific Ethernet
media components
Enclosure
Type Quick Connect
Knockout
Type Operator
Illumination
Voltage
Contact
Configuration
Cat. No.
Plastic
Mini Receptacle Metric Twist to Release
24V AC/DC
1 N.C./1 N.O.
800F-1YMQ4
Metal 24V AC/DC 800F-1MYMQ4

Table of Contents