138 Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 4 Bulletin 290E/291E/294E Programmable Parameters
Starter Protection Group
The functions highlighted are enabled by default
ProtFltResetMode
This parameter configures the Protection
Fault reset mode.
0 = Manual
1 = Automatic
Parameter Number 41
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0
ProtectFltEnable
This parameter enables the Protection
Fault by setting the bit to 1.
Parameter Number 42
Access Rule GET/SET
Data Type WORD
Group Starter Protection
Units
Minimum Value 0
Maximum Value 0xFFFF
Default Value 0xBFFF
Bit
Function
1514131211109876543210
——————————————— X
OverloadTrip
—————————————— X
PhaseShortTrip
———————————— X —— UnderPowerTrip
———————————— X ——— SensorShortTrip
——————————— X ————
OverCurrentTrip
—————————— X ————— NonVolMemoryTrip
————————— X ——————
ParamSyncTrip
———————— X ———————
DCBusTrip/
OpenDisconnect
——————— X ————————
StallTrip
—————— X ————————
OverTemperature
————— X —————————— GroundFault
———— X ———————————
RestartRetries
——— X ————————————
DriveHdwFault
—— X —————————————
OutputShortTrip
X —————————————— UserDefinedTrip
X ———————————————
HardwareFltTrip