140 Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 4 Bulletin 290E/291E/294E Programmable Parameters
User I/O Configuration Group
RunNetFltValue
This parameter determines how the starter
will be commanded in the event of a fault.
State the starter will go to on a NetFlt if
Parameter 45 (RunNetFltAction) = 1
(GotoFault-Value).
0 = OFF
1 = ON
Parameter Number 46
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0
RunNetIdlAction
This parameter in conjunction with
Parameter 48 (RunNetIdlValue) defines
how the starter will respond when
a network is idle as determined
by Parameter 48.
0 = GoToIdleValue
1 = HoldLastState
Parameter Number 47
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 1
Default Value 0
RunNetIdlValue
This parameter determines the state that
starter assumes when the network is idle
and Parameter 47 (RunNetIdlAction) is
set to 1.
0 = OFF
1 = ON
Parameter Number 48
Access Rule GET
Data Type BOOL
Group Starter Protection
Units
Minimum Value 0
Maximum Value 0x3F
Default Value 0
IOPointConfigure
This parameter determines the point
that is configured:
0 = Input
1 = Output
Parameter Number 49
Access Rule GET/SET
Data Type WORD
Group User I/O Config.
Units
Minimum Value 0
Maximum Value 0x3F
Default Value 0