EasyManua.ls Logo

Allen-Bradley ArmorStart 290E - Page 141

Allen-Bradley ArmorStart 290E
252 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012 141
Bulletin 290E/291E/294E Programmable Parameters Chapter 4
Bit
Function
5 4 3 2 1 0
X Pt00
X Pt01
X Pt02
X Pt03
X Pt04
X Pt05
FilterOffOn
This parameter determines the input
(which must be present for this time)
before being reported ON.
Parameter Number 50
Access Rule GET/SET
Data Type USINT
Group User I/O Config.
Units msecs
Minimum Value 0
Maximum Value 64
Default Value 0
FilterOnOff
This parameter determines the input
(which must be absent for this time)
before being reported OFF.
Parameter Number 51
Access Rule GET/SET
Data Type USINT
Group User I/O Config.
Units msecs
Minimum Value 0
Maximum Value 64
Default Value 0
OutProtFltState
This parameter in conjunction with
Parameter 53 (OutProtFltValue) defines
how the starter outputs will respond
when a fault occurs.
0 = GoToPrFltValue
1 = IgnorePrFlt
Parameter Number 52
Access Rule GET/SET
Data Type BOOL
Group User I/O Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0

Table of Contents

Related product manuals