116 Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 4 Bulletin 290E/291E/294E Programmable Parameters
Bit
Function
5 4 3 2 1 0
X Pt00
X Pt01
X Pt02
X Pt03
X Pt04
X Pt05
FilterOffOn
This parameter determines the input
(which must be present for this time)
before being reported ON.
Parameter Number 50
Access Rule GET/SET
Data Type USINT
Group User I/O Config.
Units msecs
Minimum Value 0
Maximum Value 64
Default Value 0
FilterOnOff
This parameter determines the input
(which must be absent for this time)
before being reported OFF.
Parameter Number 51
Access Rule GET/SET
Data Type USINT
Group User I/O Config.
Units msecs
Minimum Value 0
Maximum Value 64
Default Value 0
OutProtFltState
This parameter in conjunction with
Parameter 53 (OutProtFltValue) defines
how the starter outputs will respond when
a fault occurs.
0 = GoToPrFltValue
1 = IgnorePrFlt
Parameter Number 52
Access Rule GET/SET
Data Type BOOL
Group User I/O Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0