EasyManua.ls Logo

Allen-Bradley ArmorStart 290E - Page 128

Allen-Bradley ArmorStart 290E
252 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
128 Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 4 Bulletin 290E/291E/294E Programmable Parameters
Bit
Function:
1514131211109876543210
——————————————— X RunForward
—————————————— X RunReverse
————————————— X —— Out00
———————————— X ——— Out01
——————————— X ———— Out02
—————————— X ————— Out03
————————— X —————— Out04
———————— X ——————— Out05
——————— X ——————— JogForward
—————— X ————————— JogReverse
————— X —————————— Accel2
———— X ——————————— Decel2
——— X ———————————— Command Freq
X X X ————————————— Reserved
OutputSourceV (IPS)
[SwitchedVolts]
This parameter determines the incoming
switched control voltage across terminals
A1…A2.
(IPS) available voltage on User Output Pin
4 for all I/O points.
Parameter Number 11
Access Rule GET
Data Type UINT
Group Basic Status
Units x.xx Volts
Minimum Value 0
Maximum Value 65535
Default Value 0
SensorSourceV (IPS)
[UnswitchedVolts]
This parameter determines the incoming
unswitched control voltage across
terminals A2…A3.
(IPS) available voltage on input Sensor
Source Pin 1 for all I/O points.
Parameter Number 12
Access Rule GET
Data Type UINT
Group Basic Status
Units x.xx Volts
Minimum Value 0
Maximum Value 65535
Default Value 0

Table of Contents