EasyManua.ls Logo

Allen-Bradley ArmorStart 290E - Page 154

Allen-Bradley ArmorStart 290E
252 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
154 Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 4 Bulletin 290E/291E/294E Programmable Parameters
Figure 56 - Boost Select
MaximumVoltage
Sets the highest voltage the drive will output.
Parameter Number 87
Related Parameters
Access Rule GET/SET
Data Type UINT
Group Advanced Config.
Units V AC
Minimum Value 20V AC
Maximum Value 460V AC
Default Value 2V AC
MotorNamePlateFLA
Set to the motor nameplate Full Load Amps.
For 0.5 Hp units – Min = 0; Max = 3.0; Default = 1.5
For 1.0 Hp units – Min = 0; Max = 5.0; Default = 2.5
For 2.0Hp units – Min = 0; Max = 8.4; Default = 3.6
Parameter Number 88
Related Parameters
Access Rule GET/SET
Data Type UINT
Group Advanced Config.
Units x.x Amps
Minimum Value 0.0
Maximum Value Hp Dependent
Default Value Hp Dependent
1/2 [Motor NP Volts]
%P28 [Motor NP Volts]
%P29 [Motor NP Hertz]
[Motor NP Hertz]
1/2
0 50 100
100
50
Settings
5-14
4
3
2
1

Table of Contents

Related product manuals