EasyManua.ls Logo

Allen-Bradley ArmorStart 290E - Page 175

Allen-Bradley ArmorStart 290E
252 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012 175
Specifications Chapter 6
Environmental Ratings
Operating Temperature Range
-20…+40°C (-4…+104°F)
50 °C (122 °F) without derating, when properly rated line reactors are installed
in branch circuit.
Storage and Transportation
Temperature Range
–25...+85 °C (–13…+185 °F)
Altitude 1000 m
Humidity 5…95% (non-condensing)
Pollution Degree 3
Enclosure Ratings IP66/UL Type 4/12
Approximate Shipping Weight 7.3 kg (16 lb)
IP66/UL Type 4 is available with gland options G1-3. IP66/ UL Type 4/12 available with G1 and G3 gland option.
Mechanical Ratings
Resistance to Shock
Operational 30 G (exceeds IEC 61800-5-1)
Non-Operational 50 G (exceeds IEC 61800-5-1)
Resistance to Vibration
Operational 2.5 G, MIL-STD-810G, (exceeds IEC 61800-5-1)
Non-Operational 5 G, MIL-STD-810G, (exceeds IEC 61800-5-1)
Disconnect Lock Out Maximum of 3/8 in. (9.5 mm) diameter lock shackle or hasp
Disconnect LOTO Locks Up to 2 locks or hasps are supported
Disconnect Mechanical Life 200 000 operations
Power Terminals Motor Terminals Control Terminals PE/Ground Source Brake
Wire Size
(2) #18 …#10 AWG
(0.8…5.2 mm
2
) per
terminal
#18…#10 AWG
(0.8…5.2 mm
2
) per
terminal
(2) #18 …#10 AWG
(0.8…5.2 mm
2
) per
terminal
(2) #16 …#10 AWG
(1.3…5.2 mm
2
) per
terminal
#16 …#10 AWG
(1.0…4.0 mm
2
) per
terminal
Wire Type Multi-strand copper wire
Tightening Torque 10.6 ± 2 lb•in (1.2 ± 0.2 N•m)
18 ± 2 lb•in
(2 ± 0.2 N•m)
4.8 ± 2 lb•in
(0.5 ± 0.2 N•m)
Wire Strip Length 0.35 ± 0.01 in. (9 ± 2 mm)
Power Rating 600V AC/25 Amp 600V AC/10 Amp 600V AC/10 Amp 600V AC/10 Amp
Emission and Immunity Ratings
Emission
Conducted
EN 55011
Class Group 2
Radiated
Electrostatic Discharge 4 kV contact, 8 kV air
Radio Frequency Electromagnetic Field
EN 61800-3
10V/m, 80 MHz…1 GHz
Immunity
Fast Transient
2 kV (Power)
2 kV (PE)
1 kV (Communication and control)
Surge Transient 1 kV (12)
L-L
, 2 kV (2)
L-N
(earth)
Radio Frequency Conducted Disturbance 10V, 150 kHz…80 MHz
When two wires used in terminal block both wires are to be of same wire AWG

Table of Contents