Publication 1756-PM004C-EN-P - October 2009 57
Force I/O Chapter 3
Check Force Status
Before you use a force, determine the status of forces for the controller. You
can check force status.
The Online toolbar shows the status of forces. It shows the status of
I/O forces and SFC forces separately.
To determine status Use any of the following
I/O forces Online toolbar
FORCE status indicator
GSV instruction
SFC forces Online toolbar
Forces tab
This Means
Enabled If the project contains any forces of this type, they are
overriding your logic.
If you add a force of this type, the new force immediately
takes effect
Disabled Forces of this type are inactive. If the project contains any
forces of this type, they are not overriding your logic.
Installed At least one force of this type exists in the project.
None Installed No forces of this type exist in the project.