Rockwell Automation Publication 2080-UM002K-EN-E - March 2019 309
Troubleshooting Appendix E
0xF27z
(2)
Recoverable A non-recoverable communication fault has
occurred on the expansion I/O module.
Perform one of the following:
• See Corrective Actions for Recoverable Faults
on page 313.
• Replace the slot number z module.
0xF28z
(2)
Recoverable Expansion I/O baudrate error. Perform one of the following:
• See Corrective Actions for Recoverable Faults on page 313.
• Replace the slot number z module.
0xF29z
(2)
Recoverable A module fault is detected on your expansion I/O
module.
Perform one of the following:
• See Corrective Actions for Recoverable Faults
on page 313.
• Replace the slot number z module.
0xF2Az
(2)
Recoverable Expansion I/O power failure Perform one of the following:
• See Corrective Actions for Recoverable Faults
on page 313.
• Replace the slot number z module.
0xF2Bz
(2)
Recoverable Expansion I/O configuration fault. Perform one of the following:
• See Corrective Actions for Recoverable Faults on page 313.
• Correct the expansion IO module configuration in the user program
to match that of the actual hardware configuration.
• Check the expansion I/O module operation and condition.
• Replace the expansion I/O module.
0xF300 Recoverable The memory module is present but memory
module is empty and restore operation is
requested.
Perform the following:
• See Corrective Actions for Recoverable Faults
on page 313.
• Check to make sure there is a valid project in the memory module.
• Download a user program and use the backup function to the
memory module.
0xF301 Recoverable The memory module’s project is not compatible
with the controller.
Perform one of the following:
• See Corrective Actions for Recoverable Faults
on page 313.
• Check to make sure there is a user program with a controller that
has the correct controller catalog configured.
• Download a user program and use the backup function to the
memory module.
0xF302 Recoverable The password is mismatched between memory
module and controller. Only applies to Micro820
controller when Remote LCD performs the restore
operation.
This fault does not apply to Micro800 controller
firmware revision 10 and later.
Perform one of the following:
• See Corrective Actions for Recoverable Faults
on page 313.
• Check to make sure that the user program in the memory module
has the correct password.
• Download a user program with a password and use the backup
function to the memory module.
• Use Connected Components Workbench to enter the correct
password into the controller and perform the restore operation
again.
0xF303 Recoverable The memory module is not present and restore
operation is requested.
Check to make sure the memory module is present.
List of Error Codes for Micro800 controllers
Error Code Fault Type Description Recommended Action

Table of Contents

Other manuals for Allen-Bradley Micro830

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley Micro830 and is the answer not in the manual?

Allen-Bradley Micro830 Specifications

General IconGeneral
BrandAllen-Bradley
ModelMicro830
CategoryController
LanguageEnglish

Related product manuals