Installation/Wiring 1-7
Table 1.D Minimum Recommended Branch Circuit Protective Devices
Voltage
Rating
Drive Rating
kW (HP)
Fuse Rating
(1)
Amps
(Line Fuse)
(2)
140M
(3)
(4)
Catalog No.
Recommended
MCS Contactors
Catalog No.
Min. Enclosure
Volume
(5)
Inches
3
120V AC –
1-Phase
0.2 (0.25)
0.4 (0.5)
0.75 (1.0)
1.1 (1.5)
10
15
30
40
140M-C2E-C10
140M-C2E-C16
140M-D8E-C20
140M-F8E-C32
100-C09
100-C12
100-C23
100-C37
1655
1655
1655
1655
240V AC –
1-Phase
NO BRAKE
0.2 (0.25)
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
6
10
15
25
30
140M-C2E-B40
140M-C2E-B63
140M-C2E-C16
140M-C2E-C16
140M-D8E-C25
100-C09
100-C09
100-C12
100-C16
100-C23
1655
1655
1655
1655
1655
240V AC –
1-Phase
0.2 (0.25)
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
10
10
15
30
140M-C2E-B63
140M-C2E-B63
140M-C2E-C16
140M-D8E-C20
100-C09
100-C09
100-C12
100-C23
1655
1655
1655
1655
240V AC –
3-Phase
0.2 (0.25)
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
3.7 (5.0)
3
6
10
15
25
30
140M-C2E-B25
140M-C2E-B40
140M-C2E-C10
140M-C2E-C16
140M-C2E-C16
140M-F8E-C25
100-C09
100-C09
100-C09
100-C12
100-C16
100-C23
1655
1655
1655
1655
1655
1655
480V AC –
3-Phase
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
3.7 (5.0)
3
6
10
15
15
140M-C2E-B25
140M-C2E-B40
140M-C2E-B63
140M-C2E-C10
140M-C2E-C16
100-C09
100-C09
100-C09
100-C09
100-C16
1655
1655
1655
1655
1655
(1)
Recommended Fuse Type: UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.
(2)
EN61800-5-1 compliance
When using a dynamic brake resistor, the guidelines listed below must be followed.
– Only use input fuse UL Class T 600V or equivalent for branch circuit protection.
– Connect a series fuse, type PV 1000V fast-acting or equivalent, with the dynamic brake resistor.
– Recommended fuse rating is listed in Table B.C
.
(3)
The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M
Motor Protection Circuit Breakers Application Ratings.
(4)
Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240
Wye or Delta, 480Y/277 or 600Y/347. Not UL listed for use on 480V or 600V Delta/Delta, corner
ground, or high-resistance ground systems.
(5)
When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be
installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this
column. Application specific thermal considerations may require a larger enclosure.