Supplemental Drive Information A-3
(1)
200-240V AC - 1-Phase drives are also available with an integral EMC filter. Catalog suffix changes from N103 to N113
and N104 to N114.
(2)
The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection
Circuit Breakers Application Ratings.
(3)
Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/
277 or 600Y/347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.
(4)
When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or
non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal considerations
may require a larger enclosure.
Category Specification
Environment Altitude: 1000 m (3300 ft) max. without derating
Maximum Surrounding Air
Temperature without derating:
IP20:
NEMA 1:
Flange Mount:
–10 to 50° C (14 to 122° F)
–10 to 40° C (14 to 104° F)
Heatsink: –10 to 40° C (14 to 104° F)
Drive: –10 to 50° C (14 to 122° F)
Cooling Method
Convection:
Fan:
0.2 kW (0.25 HP) drives
Flange Mount drives, all ratings
All other drive ratings.
Storage Temperature: –40 to 85 degrees C (–40 to 185 degrees F)
Atmosphere: Important: Drive must
not be installed in an
area where the ambient atmosphere contains
volatile or corrosive gas, vapors or dust. If the
drive is not going to be installed for a period of
time, it must be stored in an area where it will not
be exposed to a corrosive atmosphere.
Relative Humidity: 0 to 95% non-condensing
Shock (operating): 15G peak for 11ms duration (±1.0ms)
Vibration (operating): 1G peak, 5 to 2000 Hz
Sound Pressure Level
(A-weighted)
Frame A:
Frame B:
Measurements are taken 1 m from the drive.
Maximum 50 dBA
Maximum 51 dBA
Control Carrier Frequency 2-16 kHz. Drive rating based on 4 kHz.
Frequency Accuracy
Digital Input:
Analog Input:
Within ±0.05% of set output frequency.
Within 0.5% of maximum output frequency.
Speed Regulation - Open Loop
with Slip Compensation:
±2% of base speed across a 40:1 speed range.
Stop Modes: Multiple programmable stop modes including -
Ramp, Coast, DC-Brake, Ramp-to-Hold and
S Curve.
Accel/Decel: Two independently programmable accel and
decel times. Each time may be programmed from
0 - 600 seconds in 0.1 second increments.
Intermittent Overload: 150% Overload capability for up to 1 minute
200% Overload capability for up to 3 seconds
Electronic Motor Overload
Protection
Provides class 10 motor overload protection
according to NEC article 430 and motor
over-temperature protection according to NEC
article 430.126 (A) (2). UL 508C File 29572.

Table of Contents

Other manuals for Allen-Bradley PowerFlex 4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 4 and is the answer not in the manual?

Allen-Bradley PowerFlex 4 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 4
CategoryController
LanguageEnglish

Related product manuals