Rockwell Automation Publication 20A-IN009E-EN-P - January 2015 27
PowerFlex 70 Adjustable Frequency AC Drive
20AD022 D 15 10 19.9 16.6 22 24.2 33 25 45 25 80 80 30 140M-D8E-C25 140M-F8E-C25 5098
20AD027 D 20 15 24.8 20.6 27 33 44 35 60 35 100 100 50 140M-F8E-C32 5098
20AD034 D 25 20 31.2 25.9 34 40.5 54 40 70 40 125 125 50 140M-F8E-C45 5098
20AD040 D 30 25 36.7 30.5 40 51 68 50 90 50 150 150 50 140M-F8E-C45 5098
20AD052 E 40 30 47.7 39.7 52 60 80 60 110 60 200 200 70
20AD065 E 50 40 59.6 49.6 65 78 104 80 125 80 250 250 100
See page 29
for notes.
Table 9 - 400/480 Volt AC Three-phase Input Drive Ratings and Input Protection Devices (Continued)
Cat.No.
Frame
(1)
Hp
Rating
Input
Ratings Output Amps
Dual
Element Time
Delay Fuse
Non-time
Delay Fuse
Circuit
Breaker
(4)
Motor
Circuit
Protector
(6)
140M Motor Protector with Adjustable Current Range
(7)
(8)
ND HD Amps kVA Cont. 1 Min. 3 Sec. Min
(2)
Max
(3)
Min
(2)
Max
(3)
Max
(5)
Max
(5)
Available Catalog Numbers
(9)
Minimum
Enclosure Volume
(in.
3
)
(10)
Table 10 - 600 Volt AC Three-phase Input Drive Ratings and Input Protection Devices
Cat.No.
Frame
(1)
Hp
Rating
Input
Ratings Output Amps
Dual
Element Time
Delay Fuse
Non-time
Delay Fuse
Circuit
Breaker
(4)
Motor
Circuit
Protector
(6)
140M Motor Protector with Adjustable Current Range
(7)
(8)
ND HD Amps kVA Cont. 1 Min. 3 Sec. Min
(2)
Max
(3)
Min
(2)
Max
(3)
Max
(5)
Max
(5)
Available Catalog Numbers
(9)
Minimum
Enclosure Volume
(in.
3
)
(10)
600 Volt AC Input
20AE0P9 A 0.5 0.33 1.3 1.3 0.9 1.1 1.4 3 3 3 3.5 15 3 140M-C2E-B16 3441
20AE1P7 A 1 0.75 1.9 2 1.7 2 2.6 3 6 3 6 15 3 140M-C2E-B25 140M-D8E-B25 3441
20AE2P7 A 2 1.5 3 3.1 2.7 3.6 4.8 4 6 4 10 15 7 140M-C2E-B40 140M-D8E-B40 3441
20AE3P9 B 3 2 4.4 4.5 3.9 4.3 5.9 6 8 6 15 15 7 140M-D8E-B63 3441
20AE6P1 B 5 3 7.5 7.8 6.1 6.7 9.2 10 12 10 20 20 15 140M-D8E-C10 140M-F8E-C10 3441
20AE9P0 C 7.5 5 7.7 8 9 9.9 13.5 10 20 10 35 35 15 140M-D8E-C10 140M-F8E-C10 3441
20AE011 C 10 7.5 9.8 10.1 11 13.5 18 15 20 15 40 40 15 140M-D8E-C16 140M-F8E-C16 3441
20AE017 D 15 10 15.3 15.9 17 18.7 25.5 20 35 20 60 60 30 140M-F8E-C20 5098
20AE022 D 20 15 20 20.8 22 25.5 34 25 45 25 80 80 30 140M-F8E-C25 5098
20AE027 D 25 20 24.8 25.7 27 33 44 35 60 35 100 100 50 140M-F8E-C25 5098
20AE032 D 30 25 29.4 30.5 32 40.5 54 40 70 40 125 125 50 140M-F8E-C32 5098
20AE041 E 40 30 37.6 39.1 41 48 64 50 90 50 150 150 100
20AE052 E 50 40 47.7 49.6 52 61.5 82 60 110 60 200 200 100
See page 29
for notes.
Table 11 - 208/240 Volt AC Single-phase Input Drive Ratings and Input Protection Devices
Cat.No.
Frame
(1)
Hp
Rating
Input
Ratings Output Amps
Dual
Element Time
Delay Fuse
Non-time
Delay Fuse
Circuit
Breaker
(4)
Motor
Circuit
Protector
(6)
140M Motor Protector with Adjustable Current Range
(7)
(8)
ND HD Amps kVA Cont. 1 Min. 3 Sec. Min
(2)
Max
(3)
Min
(2)
Max
(3)
Max
(5)
Max
(5)
Available Catalog Numbers
(9)
Minimum
Enclosure Volume
(in.
3
)
(10)
208 Volt AC Input
20AB2P2 A 0.5 0.33 2.9 0.6 1.3 1.6 1.9 6 6 6 10 15 7 140M-C2E-B40 140M-D8E-B40 3441
20AB4P2 A 1 0.75 5.6 1 2.4 2.8 3.7 10 10 10 17.5 15 7 140M-C2E-B63 140M-D8E-B63 3441
20AB6P8 B 2 1.5 10 1.8 3.9 5.2 6.9 15 15 15 30 30 15 140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 3441
20AB9P6 B 3 2 14 2.6 5.5 6.1 8.3 20 25 20 40 40 30 140M-C2E-C16 140M-D8E-C16 140M-F8E-C16 3441
20AB015 C 5 3 16 2.9 8.6 9.6 13.3 20 35 20 70 70 30 140M-C2E-C20 140M-D8E-C20 140M-F8E-C20 3441
20AB022 D 7.5 5 23.3 4.2 12.7 13.9 19.0 30 50 30 100 100 30 140M-D8E-C25 140M-F8E-C25 5098
20AB028 D 10 7.5 29.8 5.4 16.1 19 25.3 40 70 40 125 125 50 140M-F8E-C32 5098
20AB042 D 15 10 39.8 7.2 21.5 27.8 37 60 100 60 175 175 70 140M-F8E-C45 5098
20AB054 E 20 15 57.5 10.4 31.1 36.2 48.3 80 125 80 200 200 100
20AB070 E 25 20 72.3 13.0 39.1 46.6 62 90 175 90 300 300 100
240 Volt AC Input
20AB2P2 A 0.5 0.33 2.5 0.6 1.1 1.2 1.7 3 4.5 3 8 15 3 140M-C2E-B25 140M-D8E-B25 3441
20AB4P2 A 1 0.75 4.8 1 2.1 2.4 3.2 6 9 6 15 15 7 140M-C2E-B63 140M-D8E-B63 3441
20AB6P8 B 2 1.5 8.7 1.8 3.4 4.5 6 15 15 15 25 25 15 140M-C2E-C10 140M-D8E-C10 140M-F8E-C10 3441
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
sales@aotewell.com
+86-755-8660-6182

Other manuals for Allen-Bradley PowerFlex 70

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 70 and is the answer not in the manual?

Allen-Bradley PowerFlex 70 Specifications

General IconGeneral
Input Voltage200-240V AC, 380-480V AC, 500-600V AC
Frequency Range0 - 400 Hz
Humidity5% to 95% non-condensing
Output Voltage0 to Input Voltage
Control MethodsSensorless Vector Control
CommunicationsEthernet/IP, DeviceNet, ControlNet
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Ground Fault
Operating Temperature0°C to 50°C (32°F to 122°F)
Storage Temperature-40°C to 70°C (-40°F to 158°F)
Enclosure RatingIP20, NEMA Type 1

Related product manuals