PowerFlex 700 Adjustable Frequency AC Drive Quick Start 11
• Always use copper wire.
• Wire with an insulation rating of 600V or greater is recommended.
• Control and signal wires should be separated from power wires by at
least 0.3 meters (1 foot).
• I/O terminals labeled “(–)” or “Common”
are not referenced to earth
ground and are designed to greatly reduce common mode
interference. Grounding these terminals can cause signal noise.
Table F Recommended Control Wire
Table G I/O Terminal Blocks
Step 4 Control Wiring
!
ATTENTION: Configuring an analog input for 0-20mA operation and
driving it from a voltage source could cause component damage. Verify
proper configuration prior to applying input signals.
!
ATTENTION: Hazard of personal injury or equipment damage exists
when using bipolar input sources. Noise and drift in sensitive input
circuits can cause unpredictable changes in motor speed and direction.
Use speed command parameters to help reduce input source sensitivity.
Type Wire Type(s) Description
Insulation
Rating
Signal Analog I/O Belden 8760/9460 (or equiv.) 0.750 mm
2
(18AWG), twisted
pair, 100% shield with drain
(1)
.
300V,
60° C
(140° F),
Minimum
Belden 8770(or equiv.) 0.750 mm
2
(18AWG), 3 cond.,
shielded for remote pot only.
Encoder/
Pulse I/O
Less than or equal to 30 m (98
ft.) – Belden 9728 (or equiv.)
0.196 mm
2
(24AWG),
individually shielded.
Greater than 30 m (98 ft.) –
Belden 9773(or equiv.)
0.750 mm
2
(18AWG), twisted
pair, shielded.
Digital
I/O
Unshielded Per US NEC or applicable
national or local code
– 300V,
60° C
(140° F),
Minimum
Shielded Multi-conductor shielded cable
such as Belden 8770(or equiv.)
0.750 mm
2
(18AWG), 3
conductor, shielded.
(1)
If the wires are short and contained within a cabinet which has no sensitive circuits, the use of
shielded wire may not be necessary, but is always recommended.
Name Frame Description
Wire Size Range
(1)
Torque
Maximum Minimum Maximum Recommended
I/O Terminal
Block
0-5 Signal & control
connections
2.1 mm
2
(14 AWG)
0.30 mm
2
(22 AWG)
1.36 N-m
(12 lb.-in.)
1.36 N-m
(12 lb.-in.)
Encoder Terminal
Block
(2)
0-5 Encoder power &
signal connections
0.75 mm
2
(18 AWG)
0.196 mm
2
(24 AWG)
1.36 N-m
(12 lb.-in.)
1.36 N-m
(12 lb.-in.)
SHLD Terminal 0-5 Terminating point
for wiring shields
— — 1.6 N-m
(14 lb.-in.)
1.6 N-m
(14 lb.-in.)
(1)
Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
(2)
Not available with Standard Control option.