36 Rockwell Automation Publication 750-PC108A-EN-P - April 2021
PowerFlex 755T Drives Configured to Order Program Product Information
Figure 33 - Frame 9 Configured Output Bay, Top Exit: Internal Components and Installation Connection Locations
Item Description
1
Configured bay control connectors for control connections to configured input bay (not visible in this view, located behind bay frame). Connections
must be made during installation.
2
Connections for power output to customer motor. Connected via lug to L-bracket to extruded busbar connection. In each bay, the bottom two
extruded busbars each have one 4-hole L-bracket. In the left bay, the top extruded busbar has two 2-hole L-brackets. In the right side bay, the top
extruded busbar has one 2-hole L-bracket. Connections must be made during installation.
3 AC busbar splice connection hardware for power from the drive
4 PE ground bar splice connection hardware. Ground splice connection to drive PE ground bar must be made during installation.
5 Thermostat (not visible in this view, located behind sine-wave filter capacitor bank)
6 Sine-wave filter capacitor bank
7 PE ground bar
8 Fan for airflow upward through the bay
9 Sine-wave filter reactor
10
PE ground bar with ground clamps included. Terminating point to chassis ground for motor and motor cable shield. Ground connections must be
made during installation.
2
3
4
8
6
9
1
7
10
5