Electrical Requirements
84
©
Copyright, Alliance Laundry Systems LLC - DO NOT COPY or TRANSMIT Part No. 70458301ENR7
ferrite before closing the ring so as not to pinch or damage
leads.
1
Ferrite Ring
2
Electrical Connections V.A.C.
3
Ground Wire
Figure 26
Electrical Specifications
NOTE: Wire sizes were obtained from the Canadian
Electrical Code for 75 C. wire and are intended for
use as a guideline only. Electrical connections
should be made by a qualified electrical contractor
in accordance with all applicable local and national
requirements.
NOTE: Electrical specifications below are subject to
change without notice. Always refer to product serial
plate for most current specifications of product being
installed.
NOTE: Use copper conductors only.
NOTE: Connect to individual branch circuit.
NOTE: 3 Phase Only – Each tumble dryer must be
connected to its own individual branch circuit breaker,
not fuses, to avoid the possibility of “single phasing”
and causing premature failure of the motor(s).
025, 030 and 035 Series Gas and Steam Models
Serial Plate Amps Recommended CircuitSerial Plate
Voltage
Terminal Block
Connections
Required
Nonreversing Reversing Breaker Rating Wire Size AWG
(mm2)
120V/60Hz/1ph L1, Neutral, and
ground
12.0 N/A 15A – 1 pole 14 (2.5)
208-240V/60Hz/1ph L1, L2, Neutral,
and ground
6.7 N/A 10A – 2 pole 14 (2.5)
120V/60Hz/1ph L1, Neutral, and
ground
7.5** N/A 10A – 1 pole 14 (2.5)