4
38
WARNING
The washer-extractor should be connected to an individual branch
circuit not shared with lighting or other equipment.
4
Electrical Specications WF235, IWF235, IWF055, CWF235, CWF055
235 liters / 55 pounds
Boiler Fed/Steam Heat Electric Heat
Code
Voltage
Cycle
Phase
Wire
Full Load Amps
Recommended Circuit
Breaker (US-market)
AWG/mm2
kW Standard
Heating Elements
Full Load Amps
Recommended
Circuit Breaker (US-
market)
AWG/mm2
US NON-US US NON-US
N 440-480 50/60 3 3+PE 6 15 10 14/2.5
6x3 kW
32 40 40 8/10.0
P 380-415 50/60 3 3+N+PE 16 20 20 12/4.0 43 50 50 8/10.0
Q 200-240 50/60 3 3+PE 16 20 20 12/4.0 62 70 70 4/25.0
X 200-240 50/60 1/3 2/3+PE 16 20 20 12/4.0 N/A N/A N/A N/A
Alternative Electric Heat Options
N 440-480 50/60 3 3+PE
3x3 kW +
3x2 kW
27 30 32 10/6.0
P 380-415 50/60 3 3+N+PE 40 50 50 8/10.0
Q 200-240 50/60 3 3+PE 56 60 60 6/16.0
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A N/A
N 440-480 50/60 3 3+PE
3x3 kW +
3x4 kW
36 40 40 8/10.0
P 380-415 50/60 3 3+N+PE 48 50 50 8/10.0
Q 200-240 50/60 3 3+PE N/A N/A N/A N/A
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A N/A
N 440-480 50/60 3 3+PE
6x2 kW
23 30 25 10/6.0
P 380-415 50/60 3 3+N+PE 35 40 40 8/10.0
Q 200-240 50/60 3 3+PE 48 50 50 8/10.0
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A N/A
N 440-480 50/60 3 3+PE
6x4 kW
40 50 50 8/10.0
P 380-415 50/60 3 3+N+PE 53 60 60 8/10.0
Q 200-240 50/60 3 3+PE N/A N/A N/A N/A
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A N/A
Table 5