EasyManua.ls Logo

Alpine ALP080B - User Manual

Alpine ALP080B
152 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
103448-07 - 1/16 Price - $5.00
As an ENERGY STAR
®
Partner, U.S. Boiler Company has determined that the Alpine™ Series meets the ENERGY
STAR
®
guidelines for energy efciency established by the United States Environmental Protection Agency (EPA).
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage,
injury, or loss of life. For assistance or additional information, consult a qualied installer, service agency or the
gas supplier. This boiler requires a special venting system. Read these instructions carefully before installing.
9700609
INSTALLATION, OPERATING AND
SERVICE INSTRUCTIONS FOR
ALPINE
CONDENSING HIGH EFFICIENCY
DIRECT VENT
GAS - FIRED HOT WATER BOILER
Size Range - 80 MBH through 285 MBH

Table of Contents

Questions and Answers

  • E
    elizabethwallerAug 27, 2025
    What causes a Boiler Safety Limit Open (Condition 2) on an Alpine ALP080B?
    • T
      Tamara Thompson MDAug 27, 2025
      A Boiler Safety Limit Open (Condition 2) indicates that the boiler safety limit wired to terminals J6-1, 2, or 3 is open. Potential causes include loose wiring to the limit device, an auto-reset supply high limit sensor detecting a temperature in excess of 200°F.
  • V
    Victor GonzalesAug 25, 2025
    Why is the green power light blinking on my Alpine ALP080B control?
    • Z
      Zachary McmahonAug 26, 2025
      A blinking green power light on the control indicates a control fault. The internal power supply is repeatedly starting and stopping. Try disconnecting all terminals except 24VAC to power the Control. The green light should be steady. If it is not, then the control is defective. If steady, start plugging in all the connectors while watching the green light. When faulty wiring reconnected, green light will begin to flash.
  • A
    Adam GreenAug 23, 2025
    What to do if my Alpine Boiler is not responding to heat call?
    • K
      Kevin RomeroAug 25, 2025
      If your Alpine Boiler isn't responding to a call for heat and the status and priority show standby, the boiler isn't detecting the call for heat. Check the thermostat or zone wiring for loose connections, miswiring, or a defective thermostat/zone control.