Installation
17
2.10.3 Manual Calibration modes #7, and 8 (Continued)
Settings
Adjustment
Potentiometer
RED LED Notes
Fail Safe = High Level
Time delay set to zero
(full counter clockwise – DO
NOT FORCE PAST STOP)
Time delay action = either
Turn counter clockwise
until RED LED is ON
RED LED ON Material being measured
must be below sensor at
least twelve inches
Turn clockwise until
RED LED just goes OFF
RED LED OFF
RED LED will come ON Raise material level in
vessel until sensor is
covered
Turn clockwise counting
the number of turns until
the RED LED goes OFF
(or 25 turns whichever
comes rst)
RED LED OFF
(Or 25 turns whichever
comes rst)
If red LED is not o, skip
next step
Turn counter clockwise
one half the number of
turns counted
RED LED will come ON
Calibration is
Complete
Manual Calibration
When material level can be moved
Make certain that ThePoint is in manual calibration mode #7
or 8 See Section 2.10.4