Appendix A
A3
CE Installation Supplement
440-0018-731
Sht. 2
of 2
ISSUE
4
3. Remote Installations
Sensor port must be
connected to the transmitter port by one of the
following means:
401-16 Probe Filter
Coaxial cable run in conduit.
Triaxial cable.
4. Housings
All installations require the sensor and transmitter to be located in
a closed shielded/metal housing (i.e. typically explosion-
proof or
weatherproof housings meet this requirement)
5. Sensor Type/Mounting
In all non-metallic applications the sensor must have a full
concentric shield (i.e. needs to be considered when ordering).
The sensor/sensor condulet must be grounded locally either to a
metal support structure or an equivalent earth ground.
D. Comments:
Any deviation from these installation requirements should
be reviewed with factory, prior to implementation
These instructions are essential to insure conformity with specified
EC directives.