Rear Panel Connectors and Switch
TM-F2OP-C1XN-01 1-7
Resetting the Switches
Before making any changes to the switch settings, disable the power
supply output by pushing the front panel STANDBY switch to its IN
position. This temporarily shuts down the power supply. The front panel
S/D LED turns on. Then, use any small, flat-bladed screwdriver to change
the switch settings.
Any of the eight switches on SW1 is OFF when it has been flipped up to
break contact, ON when flipped down to close contact.
Rear Panel J2 Connector
The J2 Programming and Monitoring connector is a 15-terminal wire
clamp connector located on the power supply’s rear panel. See Figure 1-4.
The J2 connector provides access to the following functions:
Remote programming of output voltage AND/OR current limit
Remote monitoring of calibrated readback signals for output voltage
and output current
Remote control of the shutdown function using a 2.5 V to 15 V signal
See Table 1-3 for the list of the J2 connector terminal numbers, their
references, and corresponding functions.
Figure 1-4
Programming and Monitoring J2 Connector
1 Remote Output Voltage Programming Select
2 Remote Output Current Limit Programming Select
3 Control Ground
4 No connection
5 Voltage Program Signal Return
6 Output Voltage Programming Input
7 Current Program Signal Return
8 Output Current Limit Programming Input
9 Voltage Monitor Signal Return
10 Output Voltage Monitor
11 Current Monitor Signal Return
12 Output Current Monitor
13 No connection
14 Shutdown (S/D) Signal Return (–)
15 S/D Input (+)

Table of Contents