EasyManua.ls Logo

Amprobe ACD-10 TRMS-PLUS - Electrical Specifications - Frequency and Capacitance; Frequency Specifications; Capacitance Specifications

Amprobe ACD-10 TRMS-PLUS
21 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13

   

400.0 mVac 350mV 10 Hz 2 kHz ±( 0.5%+4 digits)
4.000 Vac 1V 5 Hz 5 kHz ±( 0.5%+4 digits)
4.000, 40.00 Vac 32V 5 Hz 100 kHz ±( 0.5%+4 digits)
400.0 Vac 90V 5 Hz 10 kHz ±( 0.5%+4 digits)
600 Vac 500V 5 Hz 5 kHz ±( 0.5%+4 digits)
400.0 Aac 60A 40 Hz 400 Hz ±( 0.5%+4 digits)
Display counts: 5000
Resolution: 0.001Hz
Overload Protection : ACA Clamp-on jaws : AC 600A rms
continuous
Transient protection : VAC input jacks : 6.5kV (1.2/50μs surge)



 

500.0nF, 5.000μF, ±( 3.5% + 6 digits)
50.00μF, 500.0μF,
3000μF
1)
Additional 50.00nF range accuracy is not specified
2)
Accuracies with film capacitor or better
3)
Specified with battery voltage above 2.8V (approximately half full battery).
Accuracy decreases gradually to 12% at low battery warning voltage of
approximately 2.4V
Transient protection : 6.5 kV (1.2/50 μs surge)