3: USER CONFIGURABLE ITEMS
NOTE: SETTINGS ARE ADJUSTED THROUGH POWERCHUTE SOFTWARE
OR OPTIONAL SMART SLOT ACCESSORY CARDS.
FUNCTION
F
ACTORY
DEFAULT
USER SELECTABLE
CHOICES
D
ESCRIPTION
Automatic Self-
Test
Every 14 days
(336 hours)
Every 7 days
(168 hours),
On Startup Only,
No Self-Test
Set the interval at which the UPS will
execute a self-test.
UPS ID UPS_IDEN Up to eight
characters
(alphanumeric)
Uniquely identify the UPS, (i.e. server
name or location) for network
management purposes.
Date of Last
Battery
Replacement
Manufacture Date mm/dd/yy Reset this date when you replace the
battery module.
Minimum Capacity
Before Return from
Shutdown
0 percent 0, 15, 30, 45, 50, 60,
75, 90 percent
Specify the percentage to which
batteries will be charged following a
low-battery shutdown before powering
connected equipment.
Voltage Sensitivity
The UPS detects
and reacts to line
voltage distortions
by transferring to
battery operation to
protect connected
equipment.
High High sensitivity,
Medium sensitivity,
Low sensitivity
Note: In situations of poor power
quality, the UPS may frequently
transfer to battery operation. If the
connected equipment can operate
normally under such conditions,
reduce the sensitivity setting to
conserve battery capacity and service
life.
Alarm Delay
Control
Enable Enable, Mute,
Disable
Mute ongoing alarms or disable all
alarms permanently.
Shutdown Delay 90 seconds 0, 90, 180, 270, 360,
450, 540, 630
seconds
Set the interval between the time when
the UPS receives a shutdown
command and the actual shutdown.
Low Battery
Warning
2 minutes
PowerChute
software provides
automatic,
unattended
shutdown when
approximately 2
minutes of battery
operated runtime
remains.
2, 5, 8, 11, 14, 17,
20, 23 minutes
(Times are
approximate.)
The UPS will beep when 2 minutes of
battery runtime remains.
Change the low battery warning
interval setting to the time that the
operating system or system software
requires to safely shut down.

Other manuals for APC SMART-UPS 750

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the APC SMART-UPS 750 and is the answer not in the manual?

APC SMART-UPS 750 Specifications

General IconGeneral
Output Power Capacity500 Watts / 750 VA
Nominal Output Voltage120V
Nominal Input Voltage120V
Waveform TypeSine wave
Output Connections(6) NEMA 5-15R
Control panelLED status display with On Line: On Battery: Replace Battery and Overload indicators
Form FactorTower
Battery TypeLead-acid battery
Transfer Time6 ms typical
Input Frequency50/60 Hz
Output Frequency50/60 Hz
Typical Recharge Time3 hours
Interface Port(s)USB
Output Voltage120V
Communication PortsUSB