9 990-1062, Revision 1 04/01
4: USER CONFIGURABLE ITEMS
NOTE: SETTING THESE ITEMS REQUIRES SOFTWARE OR OPTIONAL HARDWARE.
FUNCTION
F
ACTORY
DEFAULT
U
SER SELECTABLE CHOICES DESCRIPTION
Automatic Self-
Test
Every 14 days
(336 hours)
Every 7 days
(168 hours),
On Startup Only, No Self-Test
This function sets the interval at which the
UPS will execute a self-test. Refer to your
software manual for details.
UPS ID UPS_IDEN Up to eight characters to define
the UPS
Use this field to uniquely identify the UPS for
network management purposes.
Date of Last Bat-
tery Replacement
Manufacture
Date
Date of Battery Replacement Reset this date when you replace the battery
module.
Minimum Capacity
Before Return from
Shutdown
0 percent 15, 30, 45, 50, 60, 75, 90 percent The UPS will charge its batteries to the speci-
fied percentage before return from a shut-
down.
Sensitivity High Medium, Low Set lower than high sensitivity to avoid low-
ered battery capacity and service life in situa-
tions where the connected equipment can tol-
erate minor power disturbances.
Duration of Low
Battery Warning
2 minutes 5, 8, 11, 14, 17, 20, 23 minutes This function sets the time before shutdown at
which the UPS issues a low battery warning.
Set it higher than the default if the operating
system needs more time for shutdown.
Alarm Control Enable Mute, Disable User can mute a present ongoing alarm or
disable all existing alarms permanently.
Shutdown Delay 90 seconds 0, 180, 270, 360, 450, 540, 630
seconds
This function sets the interval between when
the UPS receives a shutdown command and
when shutdown occurs.
Synchronized Turn-
on Delay
0 seconds 60, 120, 180, 240, 300, 360, 420
seconds
The UPS will wait the specified time after the
return of utility power before turn-on (for
example, to avoid branch circuit overload).
High Transfer Point 230V models:
253VAC
120V models:
127VAC
230V models:
257, 261,265VAC
120V models:
130, 133,136VAC
To avoid unnecessary battery usage, set the
high transfer point higher if the utility voltage
is chronically high and the connected equip-
ment is known to work under this condition.
Low Transfer Point 230V models:
208VAC
120V models:
106VAC
230V models:
204, 200, 196VAC
120V models:
103, 100, 97VAC
Set the low transfer point lower if the utility
voltage is chronically low and the connected
equipment can tolerate this condition.
Output Voltage 230V models:
230VAC
230V models:
220, 240VAC
230V models ONLY, allow the user to select
the output voltage.