29. Redundancy has been lost
30. Redundancy is below alarm threshold
31. Runtime is below alarm threshold
32. Load is above alarm threshold
33. Load is no longer above alarm Threshold
34. Minimum Runtime restored
35. Bypass is not in range (either frequency or voltage)
36. Backfeed contactor stuck in OFF position
37. Backfeed contactor stuck in ON position
38. UPS in Bypass due to Internal Fault
39. UPS in Bypass due to overload
40. System in Forced Bypass
41. Fault, Bypass Relay Malfunction
42. High DC Warning
43. High DC Shutdown
44. Low Battery Shutdown
45. Low Battery Warning
F. Controls: The following controls or programming functions shall be accomplished by use of the
display unit. Pushbutton membrane switches shall facilitate these operations.
1. Silence audible Alarm.
2. Display or set the date and time.
3. Enable or disable the automatic restart feature.
4. Transfer critical load to and from static bypass.
5. Test battery condition on demand.
6. Set intervals for automatic battery tests.
7. Adjust set points for different alarms.
8. Program the parameters for remote shutdown.
G. Potential Free (Dry) Contacts: The following potential free contacts shall be available on an
optional relay interface board:
1. Normal Operation.
2. Battery Operation.
3. Bypass Operation.
4. Common Fault.
5. Low Battery.
6. UPS Off.
H. Communication Interface Board: A communication interface board shall provide the
following communication ports which can be used simultaneously:
1. RS232 Serial Port #1.
2.8 SOFTWARE AND CONNECTIVITY
A. Network Adaptor: The Ethernet Web/SNMP Adaptor shall allow one or more network
management systems (NMS) to monitor and manage the UPS in TCP/IP network
environments. The management information base (MIB) shall be provided in DOS and UNIX
"tar" formats.
B. Unattended Shutdown:
1. The UPS, in conjunction with the network adaptor, shall be capable of gracefully shutting
down one or more operating systems.
2. The UPS shall also be capable of using an RS232 port to communicate by means of serial
communications to gracefully shut down one or more operating systems during an on
battery situation.
2.9 ACCESSORIES
A. Battery Disconnect Breaker: Each UPS system shall have a 320 A 500 V DC rated, thermal
magnetic trip molded case circuit breaker. Each circuit breaker shall be equipped shunt trip
mechanisms and 1A/1B auxiliary contacts. The circuit breakers are to be located within the
UPS enclosure or as part of a line-up-and-match type battery cabinet.

Other manuals for APC Symmetra PX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the APC Symmetra PX and is the answer not in the manual?

APC Symmetra PX Specifications

General IconGeneral
Noise level61 dB
Output power32000 W
Output power capacity32 kVA
Emergency Power Off (EPO)Yes
Battery typeVRLA
Dimensions (WxDxH)1200 x 1070 x 1991 mm
Battery technologySealed Lead Acid (VRLA)
Battery recharge time3.5 h
CertificationEN 50091-1, EN/IEC 62040-3, EN/IEC 62040-1-1, FCC Part 15 Class A, VFI-SS-111
Product colorBlack
Operating altitude0 - 999.9 m
Non-operating altitude0 - 15000 m
Storage temperature (T-T)-15 - 40 °C
Operating temperature (T-T)0 - 40 °C
Operating relative humidity (H-H)0 - 95 %
Weight and Dimensions IconWeight and Dimensions
Weight1095400 g
Package weight1189000 g