Page 7 1/25/2013
B. PDU-XR: The maintenance bypass cabinet shall provide power to the critical load bus from
the bypass source, during times where maintenance or service of the UPS is required. 315A
GL fuse must be in front of the mains input and if dual mains a 250 A gL fuse on the bypass
input must be installed.
C. Wall-mount Maintenance Bypass Panel: The wall-mount maintenance bypass panel
provides maintenance bypass without modular power distribution or batteries.
PART 3 – EXECUTION
3.1 REMOTE UPS MONITORING
The following three methods of remote UPS monitoring shall be available:
A. Web Monitoring: Remote monitoring shall be available via a web browser such as
Internet Explorer.
B. RS232 Monitoring: Remote UPS monitoring shall be possible via either RS232 or contact
closure signals from the UPS.
C. Simple Network Management Protocol (SNMP): Remote UPS Monitoring shall be possible
through a standard MIB II compliant platform.
3.2 SOFTWARE COMPATIBILITY
A: The UPS manufacturer shall have available software to support graceful shutdown and remote
monitoring for the following systems:
1. Microsoft Windows 95/98/XP
2. Microsoft Windows NT 4.0 SP6/2000
3. OS/2
4. Netware 3.2 – 5.1
5. MAC OS 9.04, 9.22, 10
6. Digital Unix/True 64
7. SGI 6.0-6.5
8. SCO UNIX
9. SVR4 2.3, 2.41
10. SCO Unix Ware 7.0 - 7.11
11. SUN Solaris 2.6-2.8
12. SUN OS 4.13, 4.14
13. IBM AIX 4.3x-4.33g, 5.1
14. HP-UX 9.x-11.i
3.3 STANDARD AND TESTS
A. Standards: All equipment shall be designed and built in accordance with accepted engineer-
ing practice and applicable international standards, in particular the standards listed below.
1. 89/336/EEC
2. 73/23EEC
3. EN/IEC62040-1-1, EN/IEC/UL60950-1
4. EN50091-2 / IEC62040-2 (class A), FCC15A
5. IEC EN/IEC62040-3
6. VFI-SS-111
7. IEC62040-2 / EN/IEC 61000-4-2 level 3, APC performance criteria A
8. IEC62040-2 / EN/IEC 61000-4-4 level 2, APC performance criteria A
9. IEC62040-2 / EN/IEC 61000-4-3 level 2, APC performance criteria A
10. IEC62040-2 / EN/IEC 61000-4-5 Level 3, APC performance criteria A
3.4 FACTORY ASSISTED START-UP
If a factory assisted UPS start-up is requested, factory trained service personnel shall perform
the following inspections, test procedures, and on-site training:
A. Visual Inspection:
1. Inspect equipment for signs of damage.

Other manuals for APC Symmetra PX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the APC Symmetra PX and is the answer not in the manual?

APC Symmetra PX Specifications

General IconGeneral
Noise level61 dB
Output power32000 W
Output power capacity32 kVA
Emergency Power Off (EPO)Yes
Battery typeVRLA
Dimensions (WxDxH)1200 x 1070 x 1991 mm
Battery technologySealed Lead Acid (VRLA)
Battery recharge time3.5 h
CertificationEN 50091-1, EN/IEC 62040-3, EN/IEC 62040-1-1, FCC Part 15 Class A, VFI-SS-111
Product colorBlack
Operating altitude0 - 999.9 m
Non-operating altitude0 - 15000 m
Storage temperature (T-T)-15 - 40 °C
Operating temperature (T-T)0 - 40 °C
Operating relative humidity (H-H)0 - 95 %