Page 8 1/25/2013
2. Verify installation per manufacturer s instructions.
3. Inspect cabinets for foreign objects.
4. Inspect Battery Units.
5. Inspect Power Modules.
B. Mechanical Inspection:
1. Check all UPS and external maintenance bypass cabinet internal control wiring connec-
tions.
2. Check all UPS and external maintenance bypass cabinet internal power wiring connections.
3. Check all UPS and external maintenance bypass cabinet terminal screws, nuts, and/or
spade lugs for tightness.
C. Electrical Inspection:
1. Verify correct input and bypass voltage.
2. Verify correct phase rotation of all mains connections.
3. Verify correct UPS control wiring and terminations.
4. Verify voltage of all battery modules.
5. Verify neutral and ground conductors are properly landed.
6. Inspect external maintenance bypass switch for proper terminations and phasing.
D. Site Testing:
1. Ensure proper system start-up.
2. Verify proper firmware control functions.
3. Verify proper firmware bypass operation.
4. Verify proper maintenance bypass switch operation.
5. Verify system set points.
6. Verify proper inverter operation and regulation circuits.
7. Simulate utility power failure.
8. Verify proper charger operation.
9. Document, sign, and date all test results.
E. On-Site Operational Training: During the factory assisted start-up, operational training for
site personnel shall include key pad operation, LED indicators, start-up and shutdown proce-
dures, maintenance bypass and AC disconnect operation, and alarm information.
3.5 MANUFACTURER FIELD SERVICE
A. Worldwide service: The UPS manufacturer shall have a worldwide service organization
Available, consisting of factory trained field service personnel to perform start-up, preventative
maintenance, and service of the UPS system and power equipment. The service organization
shall offer 24 hours a day, 7 days a week, 365 days a year service support.
B. Replacement parts: Parts shall be available through the worldwide service organization 24
hours a day, 7 days a week, 365 days a year. The worldwide service organization shall be ca-
pable of shipping parts within 4 working hours or on the next available flight, so that the parts
may be delivered to the customer site within 24 hours.
C. Maintenance contracts: A complete offering of preventative and full service maintenance con-
tracts for the UPS system and the battery system shall be available. All contract work shall be
performed by APC factory trained service personnel.
3.6 TRAINING
A. UPS service training workshop: A UPS service training workshop shall be available from the
UPS manufacturer. The service training workshop shall include a combination of lecture and
practical instruction with hands-on laboratory sessions. The service training workshop shall in-
clude instruction about safety procedures, UPS operational theory, sub-assembly identification
and operation, system controls and adjustment, preventative maintenance, and troubleshoot-
ing.
END OF SECTION

Other manuals for APC Symmetra PX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the APC Symmetra PX and is the answer not in the manual?

APC Symmetra PX Specifications

General IconGeneral
Noise level61 dB
Output power32000 W
Output power capacity32 kVA
Emergency Power Off (EPO)Yes
Battery typeVRLA
Dimensions (WxDxH)1200 x 1070 x 1991 mm
Battery technologySealed Lead Acid (VRLA)
Battery recharge time3.5 h
CertificationEN 50091-1, EN/IEC 62040-3, EN/IEC 62040-1-1, FCC Part 15 Class A, VFI-SS-111
Product colorBlack
Operating altitude0 - 999.9 m
Non-operating altitude0 - 15000 m
Storage temperature (T-T)-15 - 40 °C
Operating temperature (T-T)0 - 40 °C
Operating relative humidity (H-H)0 - 95 %
Weight and Dimensions IconWeight and Dimensions
Weight1095400 g
Package weight1189000 g