13. PARAMETER SETTING with ONBOARD KEYPAD
The type of door speed setting.
Normally, only factory default values , or can be selected. Besides
“ ” values appears if any custom setting has been done by user via KM-
20 Keypad under speed settings.
Speed setting parameters will be set to slow default values.
Speed setting parameters will set to normal default values.
Speed setting parameters will set to fast default values.
The custom setting has been done by user via KM-20 Keypad. If no
custom setting is made, this value will not appear.
The maximum opening-closing force applied to overcome an obstacle.
Door is in test operation. Door opens and closes continuously with a few
seconds intervals. The control signals (open, close etc.) will be ignored.
The reopening signals (photocell or obstacle detection) are still functional.
Door is in normal operation.
The type of door control signals.
The door controller will be controlled by two separate inputs. 24Vdc
voltage applied to terminal “Close” will cause the doors to close. And
terminal “Open” will cause the door to open. If no signal is applied, the
door remains its position. If both inputs are applied the close signal has
priority.
The door controller will be controlled by a single input. Only “Close”
signal is used and “Open” signal is not used. 24Vdc voltage applied to
terminal “Close” will cause the doors to close. Interrupting the voltage
causes the door to open. During the absence of voltage the door remains
open.
Note: According to the EN81 door movement must be prevented when
emergency stop, inspection or recall modes engaged. This adjustment can
only made for old door units.