42
4
Press
key to turn on the load.
0.000V 0.000A
200.00
W CPV ON
Solution 2:
Procedures Operation Descriptions Display
1
Move the cursor to the hundredths with
key.
0.000V 0.000A
1
00.00W CPV OFF
2 Rotate the knob to set the hundredths to 2.
(Rotating the knob will change the set value
immediately. The set value will become effective at
input at once when the load is turned on.)
0.000V 0.000A
2
00.00W CPV OFF
3
Press
key to turn on the load.
0.000V 0.000A
2
00.00W CPV ON
For the above operating procedures, the corresponding SCPI commands should be:
MODE CPV ;Sets the mode
POW 200 ;Sets the power value
INP ON ;Turns on the load
Note: CPV /CPC will be shown respectively in the lower right corner of the display when the load
is in CPV or CPC mode.
4.6 Short Circuit Operation
The operating procedures for short circuit operation are shown below:
1. Press
key to enter into main menu, and select Short (short circuit) item with
key.
2. Use
key or knob to set On, and press key to confirm.
3. Press
key to exit the main menu. The display shows “s” to indicate in the basic test
mode.
4. Press
key to enter into the mode selection and parameter setting menu; use ,
keys to select one basic operating mode; press key to confirm and exit the mode
selection and parameter setting menu.
5. Press key to turn on the load.
Example 1: The load was in CV mode previously and it is turned off. Set the load to short circuit
in CCH status. Turn on the load to execute short circuit operation.
Procedures Operation Descriptions Display
1
Press
key to enter into main menu, and select Short
Short:
On *Off