8
asberprofessional.com
2.5.3
Testing de gas supply piping system
.
When test pressures exceed ½ PSI (3.45 kPa), the fryer and its individual shutoff valve must be
disconnected from the gas supply piping system.
When test pressures are ½ PSI (3.45 kPa) or less, the fryer must be isolated from the gas
supply piping system by closing its individual shutoff valve.
2.5.4 This appliance is equipped for natural gas.
This appliance is equipped with orifices sized (# 36) for operation with natural gas.
For conversion to LP (PROPANE) gas see instruction plate in the appliance. Gas conversion
must be performed by qualified or authorized personnel. Orifices (#52) necessary for LP
(PROPANE) and regulator for conversion are provided on accessory box.
2.5.5 Presureregulator conversión:
Failure to install the pressure regulator will void the appliance
warranty
The fryer needs to be restrained to prevent tipping when installed in order to avoid the splashing
of hot liquid. Install the fryer connection to a battery of appliances or installing the fryer in an
alcove, or by separate means, such as adequate ties.
A. Remove cap and snap out plastic plunger from bottom of cap.
B. Turn plunger over and snap back in original location.Please see in the
last three pages of this manual the gas conversion instructions.