14 Chapter 3 operation
Series 230 Automatic Transfer Switch C1000 Intelligent Controller User Manual
The DIP switch is used for various parameter settings, and the definitions are shown in Table 3-2. “X” in the table
means unconcerned.
Table 3-2 DIP Switch Illustration
Setting Bit1
Bit2
Bit3
Bit4
Bit5
Bit6
Bit7
Bit
8
Parameter Defa
ult
Rated Voltage OFF
OFF
X X X X X X 220V or 380V OFF,
OFF
ON OFF
X X X X X X 230V or 400V
OFF
ON X X X X X X 240V or 415V
ON ON X X X X X X
Rated
Frequency
X X OFF
X X X X X 50Hz OFF
X X ON X X X X X 60Hz
Under-Voltage
dropout
X X X OFF
X X X X Under-voltage dropout
=85%
OFF
X X X ON X X X X Under-voltage dropout
=70%
Center Position
protection
X X X X OFF
X X X Center position
protection disable
OFF
X X X X ON X X X Center position
protection enable
Center Position
Time Delay
X X X X X OFF
X X Disable OFF
X X X X X ON X X Delay 5 seconds
Control Mode X X X X X X OFF
OF
F
Source I Priority, OFF
OFF
X X X X X X ON OF
F
No Source Priority
X X X X X X OFF
O
N
Remote control mode
X X X X X X ON O
N
Manual control mode
*Over Trip Setting: Set the DIP Switch bit1-2 to ON,ON. The RUN indicator is OFF and ALARM indicator is ON that means enter
over voltage trip setting mode. One of Position I and Position II indicators is flashing. Position I indicator flashing indicates over
voltage trip is disbaled. Position II indicator flashing indicates over voltage is enabled. Press Key to switch the setting. Set DIP Switch
to Rated Voltage shall exit this setting mode.
3.5 Communication Port for Setting
There is a communication port on the bottom edge of the panel covered by a rubber cover. When the rubber cover is
uncovered, there are a square hole and a 6-needle connector under it, as shown in Figure 3-4.
Figure 3-4 Communication Port
Rubber cover Square hole