Chapter 1 Overview 3
Series 230 Automatic Transfer Switch C1000 Intelligent Controller User Manual
Electromagnetic immunity performance parameters of C1000 controller:
Table 1-5 Electromagnetic Immunity Performance Parameters
Item Requirements & Criterion Standard
Surge immunity
Criterion: A
AC inputs Port
:±
2KV
DC port
:±
800V
Signal Port
:±
2kV
EN 61000-4-5
Immunity to Electrical Fast Transient
Level 3
Criterion: A
Power Port: 2kV
Signal Port: 1kV
EN 61000-4-4
Immunity to Electrostatic Discharge
Criterion: A
Contact discharge: 6kV
Air discharge :8kV
IEC61000-4-2
Immunity to Radiated Electric Fields
Criterion: A
10V/m, 80MHz - 1GHz
IEC61000-4-3
Immunity to Continuous Conducted
Interference
Criterion: A
Power Port: 10V
Signal Port: 10V, 150 kHz - 80MHz
EN 61000-4-6
Certification requirements of C1000 controller:
Table 1-6 Certification Requirements
Certification Categories Standard
CE EN60947-6-1
IEC IEC60947-6-1
1.4 Accessory Information
Please check and make sure you have received all the accessory items in Table 1-7. These are included as standard
with your C1000 Controller.
Table 1-7 Accessories included with Standard C1000 Controller
Standard Accessory Description Model / Specification Part Number Quantity Comments
Grounding Cable LTS C1000 SL1 04110332 1 Length: 200mm
Series 230 C1000 Intelligent Controller
User Manual
31012665 1
Note: Controller Power & Signal Cables are included with the ASCO Series 230 Transfer Switch Unit packaging.