Ascon Tecnologic - KX6 - ENGINEERING MANUAL - PAG. 22
Appendix A
]
inP GROUP - Main and auxiliary input configuration
no. Param. Description
Dec.
Point
Values Default
1
SEnS
Input type 0
J TC J (-50... +1000°C/-58... +1832°F);
crAL TC K (-50... +1370°C/-58... +2498°F);
S TC S (-50... 1760°C/-58... +3200°F);
r TC R (-50... +1760°C/-58... +3200);
t TC T (-70... +400°C/-94... +752°F);
0.20 0... 20 mA linear;
4.20 4... 20 mA linear;
0.60 0... 60 mV linear;
12.60 12... 60 mA linear.
J
2
dp
Decimal Point Position (linear inputs) 0 0... 3 0
3
SSc
Initial scale read-out for linear inputs dp -1999... 9999 0
4
FSc
Full Scale Readout for linear inputs dp -1999... 9999 1000
5
unit
Engineer unit °C/°F °C
6
Fil
Digital filter on the measured value 1 0 (= OFF) - 0.1... 20.0 s 1.0
7
inE
Sensor error used to enable the safety output value
or Over range;
ou Under range;
our Over and under range.
our
8
oPE
Safety output value (% of the output) -100... 100% of the oputput 0
9
diF1
Digital Input 1 function
oFF No function;
1 Alarm reset;
2 Alarm acknowledge (ACK);
3 Hold of the measured value;
4 Stand by mode;
5 Manual mode;
6 HEAt with SP1 and CooL with SP2;
7 SP1 - SP2 selection.
oFF
10
diF2
Digital Input 2 function oFF
11
di.A
Digital Inputs Action
(DI2 only if configured)
0 DI1 direct action, DI2 direct action;
1 DI1 reverse action, DI2 direct action;
2 DI1 direct action, DI2 reverse action;
3 DI1 reverse action, DI2 reverse action.
0
]
Out group
no. Param. Description
Dec.
Point
Values Default
12
o1t
Output 1 type
(when Out 1 is a linear output)
0-20 0... 20 mA;
4-20 4... 20 mA;
0-10 0... 10 V;
2-10 2... 10 V.
0-20
13
o1F
Out 1 function
(when Out 1 is a digital output)
NonE Output not used;
H.rEG Heating output;
c.rEG Cooling output.
H.rEG
14
o2F
Out 2 function (when the instrument is
equipped with 2 digital output)
NonE Output not used;
H.rEG Heating output;
c.rEG Cooling output.
15
o3AL
Alarms linked up with Out 3 0
0... 31:
+1 Alarm 1;
+2 Alarm 2;
+4 Loop break alarm;
+8 Sensor break;
+16 Potentiometer break alarm.
AL2
16
o3Ac
Out 3 action 0
dir Direct action;
rEU Reverse action;
dir.r Direct with reversed LED;
ReU.r Reverse with reversed LED.
dir
17
o4AL
Alarms linked up with the out 4 0
0... 31:
+1 Alarm 1;
+2 Alarm 2;
+4 Loop break alarm;
+8 Sensor break;
+16 Potentiometer break alarm.
AL1 +
AL2
18
o4Ac
Out 4 action 0
dir Direct action;
rEU Reverse action;
dir.r Direct with reversed LED;
ReU.r Reverse with reversed LED.
dir

Table of Contents