Ascon Tecnologic - KX6 - ENGINEERING MANUAL - PAG. 26
]
Ser group - Serial link parameters
no. Param. Description
Dec.
Point
Values Default
83
Add
Instrument address
oFF Serial link disabled;
1... 254.
1
84
bAud
Baud rate
1200 1200 baud;
2400 2400 baud;
9600 9600 baud;
19.2 19200 baud;
38.4 38400 baud
9600
85
trSP
Selection of the value to
be retransmitted (Master)
nonE Retransmission not used (the instrument is a slave);
rSP The instrument becomes a Master and retransmits the operative set
point;
PErc
The instrument become a Master and it retransmits the power output
nonE
]
cAL group - User calibration parameters
no. Param. Description
Dec.
Point
Values Default
86
AL.P
Adjust Low Point From -1999 to (AH.P - 10) in engineering units 0
87
AL.o
Adjust Low Offset -300... +300 (E.U.) 0
88
AH.P
Adjust High Point From (AL.P + 10) to 9999 engineering units 9999
89
AH.o
Adjust High Offset -300... +300 0