Ascon Tecnologic - KX6 - ENGINEERING MANUAL - PAG. 25
]
SP group - Set point parameters
no. Param. Description
Dec.
Point
Values Default
60
nSP
Number of used set points 0 1... 4 1
61
SPLL
Minimum set point value dP From -1999 to SPHL -1999
62
SPHL
Maximum set point value dP From SPLL to 9999 9999
63
SP
Set point 1 dP From SPLL to SPLH 0
64
SP2
Set point 2 dP From SPLL to SPLH 0
65
SP3
Set point 3 dP From SPLL to SPLH 0
66
SP4
Set point 4 dP From SPLL to SPLH 0
67
A.SP
Selection of the active set point 0 From 1 (SP 1) to nSP 1
68
SP.rt
Remote set point type 0
rSP The value coming from serial link is used as remote SP;
trin The value will be added to the local set point selected
by A.SP and the sum becomes the operative set point;
PErc The value will be scaled on the input range and this
value will be used as remote SP.
trin
69
SPLr
Local/remote set point selection 0
Loc Local;
rEn = Remote.
Loc
70
SP.u
Rate of rise for POSITIVE set point
change (ramp UP)
2 0.01... 99.99 (inF) engineering units per minute inF
71
SP.d
Rate of rise for NEGATIVE set point
change (ramp DOWN)
2 0.01... 99.99 (inF) engineering units per minute inF
]
PAn group - Operator HMI parameters
no. Param. Description
Dec.
Point
Values Default
72
PAS2
Level 2 password (limited
access level)
0
oFF Level 2 not protected by password;
1... 200.
20
73
PAS3
Level 3 password (com-
plete configuration level)
0 3... 200 30
74
uSrb
button function during
RUN TIME
nonE No function;
tunE Auto-tune/self-tune enabling. A single press (longer than 1 se-
cond) starts the auto-tune;
oPLo
Manual mode. The first pressure puts the instrument in manual mode
(oPLo) while a second one puts the instrument in Auto mode;
AAc Alarm acknowledge;
ASi Alarm reset;
St.by
Stand by mode. The first press puts the instrument in stand by
mode while a second one puts the instrument in Auto mode
t;
SP1.2 SP/SP2 selection.
tunE
75
diSP
Middle display management
nonE Standard display;
SPF Final set point;
Spo Operative set point;
AL1 Alarm 1 threshold;
AL2 Alarm 2 threshold;
Po Power Output
0
76
di.cL
Colour of the upper display
0 The display colour is used to show the actual deviation (PV - SP);
1 Display red;
2 Display green;
3 Display orange.
0
77
AdE
Deviation for display colour
management
1... 9999 (E.U.) 5
78
diS.t
Display Timeout 2
oFF Display always ON;
0.1... 99.59 (mm.ss).
oFF
79
fiLd
Filter on the displayed
value
1
oFF Filter disabled;
1... 100 (E.U.).
oFF
80
dSPu
Instrument status at power
ON
AS.Pr Starts in the same way it was prior to the power down;
Auto Starts in Auto mode;
oP.0 Starts in manual mode with a power output equal to zero;
St.bY Starts in stand-by mode.
AS.Pr
81
oPr.E
Operative modes enabling
ALL All modes will be selectable by the next parameter;
Au.oP Auto and manual (oPLo) mode only will be selectable by the next
parameter;
Au.Sb
Auto and Stand-by modes only will be selectable by the next parameter
ALL
82
oPEr
Operative mode selection
If oPr.E = ALL: - Auto = Auto mode;
- oPLo = Manual mode;
- St.bY = Stand by mode;
If oPr.E = Au.oP:
- Auto = Auto mode;
- oPLo = Manual mode;
If oPr.E = Au.Sb: - Auto = Auto mode;
- St.bY = Stand by mode.
Auto