EasyManua.ls Logo

Atlas Copco G 160 VSD

Atlas Copco G 160 VSD
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 Installation
4.1 Installation remarks
General
The compressor is intended for indoor use only.
Working with machinery controlled by a frequency converter requires special
safety precautions, which depend on the type of network (TN, TT or IT). Consult
Atlas Copco.
When good EMC practices for installation are followed, the compressor qualifies
for installation in EMC category C3, according to EN61800-3, for use in a 2
nd
environment (a 2
nd
environment includes all establishments other than those
directly connected to a low voltage power supply network which supplies buildings
used for domestic purposes).
Cooling air for starter cabinet:
Contamination levels (ambient) according to IEC 60721-3-3
Chemical gases: Class 3C2
Solid particles: Class 3S2
No conductive dust allowed
No condensation allowed
Maximum allowed relative humidity is 60 % in the presence of corrosive
gases
The compressor is not intended to be used on a low-voltage public network which supplies
domestic premises. Radio frequency interference can be expected if used on such a
network.
Instruction book
APF221384 43

Related product manuals