2920 1449 00
18
Instruction book
2.3 Electric cable size
50 Hz compressors 3)
Type 230 V 400 V 500 V
GR110 2x (3x150mm²+95mm²) 3x120mm²+70mm² 3x95mm²+50mm²
GR132 2x (3x185mm²+95mm²) 2x (3x95mm²+50mm²) 3x120mm²+70mm²
GR160 2x (3x240mm²+120mm²) 2x (3x120mm²+70mm²) 2x (3x70mm²+35mm²)
GR200 - 2x (3x150mm²+70mm²) 2x (3x120mm²+70mm²)
60 Hz IEC compressors 3)
Type 220/230 V 380 V 440/460 V
GR110 2x (3x150mm²+95mm²) 2x (3x70mm²+35mm²) 2x (3x50mm²+25mm²)
GR160 - 2x (3x95mm²+50mm²) 2x (3x95mm²+50mm²)
GR200 - 2x (3x150mm²+70mm²) 2x (3x120mm²+70mm²)
60 Hz CSA/UL compressors 4)
Type 440/460 V 575 V
GR110 2x (3xAWG00+AWG4) 3xAWG000+AWG3
GR160 2x (3xAWG000+AWG3) 2x (3xAWG00+AWG4)
GR200 2x (3xMCM400+AWG0) 5) or 2x (3xMCM250+AWG2) 5) or
4x (3xAWG00+AWG4) 6) 4x (3xAWG1+AWG6) 6)
2.4 Pictographs
1 Automatic operation
2 Voltage on
3 Start
4 Stop
5 Compressor locked (in off position)
6 Local control
7 Remote control (by external switches)
8 Remote control (by computer)
9 Emergency stop
10 Keys to scroll through display
11 Key to go to next field on display
12 Alarm
Fig. 2.5 Pictographs, control panel
1210 35678
9
12 11 4
50591F